4.2.2 Configuration Registers
Register Address
(protocol address)
Register Address
(PLC address)
R/W
Description
13
14
R/W
“Open Window” switch-off timeout
10
▪ 0..30 (minutes)
▪ Factory setting: 30 (minutes)
14
15
R
Modbus RTU baud-rate
▪ 2400bps
▪ 4800bps
▪ 9600bps (Default)
▪ 19200bps
▪ 38400bps
▪ 57600bps
▪ 76800bps
▪ 115200bps
15
16
R
Modbus Slave Address
▪ 1..63
21
22
R
Max number of fan speeds
48
49
R
Switch value
49
50
R
Device ID: 0x0801
50
51
R
Software version
81
82
R
Error address
▪ Provides the indoor unit’s number which is
showing the error
10
Once window contact is open, a count-down to switch off the AC Unit will start from this configured value.