4.2.3 Considerations on Temperature Registers
AC unit temperature setpoint (R/W)
(register 4 in Protocol address / register 5 in PLC address):
This is the adjustable temperature setpoint value that must be required by the user. This
register can be read (Modbus function 3 or 4) or written (Modbus functions 6 or 16). A
remote controller connected to the Daikin indoor unit will report the same temperature
setpoint value as this register, unless virtual temperature is applied.
AC unit temperature reference (R)
(register 5 in Protocol address / register 6 in PLC address):
This register reports the temperature that is currently used by the Daikin indoor unit as
the reference of its own control loop. Depending on the configuration of the indoor unit,
this value can be the temperature reported by the sensor on the return path of the Daikin
indoor unit or the sensor of its remote controller. It is a read-only register (Modbus
functions 3 or 4).
AC unit external temperature reference (Modbus) (R/W)
(register 22 in Protocol address / register 23 in PLC address):
This register allows us to provide an external temperature’s sensor from the Modbus side.
If an external temperature is provided through this register, indoor unit will use it as
reference for its temperature control loop.
o For this temperature to take effect it is required that:
a) The Daikin AC indoor unit is configured in such a way that it uses the
“thermostat sensor in the remote controller” (this is, INMBSDAI001R000
will act as thermostat sensor providing a temperature sensor reading). This
configuration is done via a Daikin remote controller connected to the indoor
unit (Config mode “10” first code value “2” second code value “1”) and
must be done by Daikin authorized installers at the time of the installation
of the AC.
Moreover, the DIP Switch SW1-P4 needs to be set as “Daikin Remote
Controller ambient temperature reading“ (On position).
b) INMBSDAI001R000 is set as “master” of P1P2 bus, with respect to an
additional remote controller in the bus (see section 2.1 Connection to the
AC indoor unit” and “4.3 DIP-Switch Configuration Interface”)
o Register value after INMBSDAI001R000 startup is -32768, which means that no
temperature reference is provided to the AC indoor unit. In that case, AC indoor
unit will use its own return path temperature sensor as reference for its control
loop.
In case the INMBSDAI001R000 is set as Master, DIP-Switch SW1-P4 is set as “Daikin
Indoor Unit ambient temperature reading (Default value)” (Off position) and consequently
the Daikin AC indoor unit is set to use its own return path temperature, any value written
in this register will not take effect.
In case the INMBSDAI001R000 is set as Slave and there is a write request from the
Modbus master to register 22/23, “Virtual temperature” will apply: