4.6 EIA-485 bus. Termination resistors and Fail-Safe Biasing mechanism
EIA-485 bus requires a 120Ω terminator resistor at each end of the bus to avoid signal reflections.
In order to prevent fail status detected by the receivers, which are listening the bus, when all
the transmitters outputs are in three-state (high impedance), it is also required a fail-safe biasing
mechanism. This mechanism provides a safe status (a correct voltage level) in the bus when all
the transmitters’ outputs are in three-state. This mechanism must be supplied by the Modbus
Master.
The INMBSDAI001R000 device includes an on-board terminator resistor of 120Ω that can be
connected to the EIA-485 bus by using DIP-switch SW4.
Some Modbus RTU EIA-485 Master devices can provide also internal 120Ω terminator resistor
and/or fail-safe biasing mechanism (check the technical documentation of the Master device
connected to the EIA-485 network in each case).