Fujitsu Air Conditioning Compatible with Domestic and VRF line air conditioners commercialized by Fujitsu USER MANUAL Issue date: 05/2021 r1.
Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN Important User Information Disclaimer The information in this document is for informational purposes only. Please inform HMS Industrial Networks of any inaccuracies or omissions found in this document. HMS Industrial Networks disclaims any responsibility or liability for any errors that may appear in this document. HMS Industrial Networks reserves the right to modify its products in line with its policy of continuous product development.
Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN Gateway for the integration of a Fujitsu air conditioning unit in ModBus RTU enabled monitoring and control systems. Compatible with Domestic and VRF line air conditioners commercialized by Fujitsu. ORDER CODE INMBSFGL001I000 LEGACY ORDER CODE FJ-AC-MBS-1 © HMS Industrial Networks S.L.U - All rights reserved This information is subject to change without notice URL https://www.intesis.
Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN INDEX 1 Presentation .......................................................................................................................................................... 5 2 Connection ............................................................................................................................................................ 6 Connect to the AC indoor unit ................................................................................
Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN 1 Presentation The INMBSFGL001I000 interfaces allow a complete and natural integration of Fujitsu air conditioners into Modbus RTU (EIA-485) networks. Reduced dimensions. 93 x 53 x 58 mm 3.7” x 2.1” x 2.3” Quick and easy installation. Mountable on DIN rail, wall, or even inside the indoor unit of AC. • External power not required. • Direct connection to Modbus RTU (EIA-485) networks.
Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN 2 Connection The interface comes with cable + connectors for direct connection to the AC indoor unit, and with a plug-in terminal block of 3 poles for connection to a Modbus RTU EIA-485 network. Connect to the AC indoor unit The INMBSFGL001I000 connects directly to the indoor unit internal control board. In the control board locate the socket connector marked as CN65.
Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN 3 Quick Start Guide 1. Disconnect the air conditioning from Mains Power. 2. Attach the interface next to the AC indoor unit (wall mounting) following the instructions of the diagram below or install it inside the AC indoor unit (respect the safety instructions given). 3. Connect to CN65 between the interface and the AC indoor unit following the instructions of the diagram. 4. Connect the EIA-485 bus to the connector EIA485 of the interface. 5.
Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN 4 Modbus Interface Specification Modbus physical layer INMBSFGL001I000 implements a Modbus RTU (Slave) interface, to be connected to an EIA-485 line. It performs 8N2 communication (8 data bits, no parity and 2 stop bit) with several available baud rates (2400 bps, 4800 bps, 9600 bps -default-, 19200 bps, 38400 bps, 57600 bps, 76800 bps and 115200 bps). It also supports 8N1 communication (8 data bits, no parity and 1 stop bit).
Intesis® Modbus RTU – Fujitsu Register Address (protocol address) Register Address (PLC address) User Manual r1.3 EN R/W Description ▪ 0..65535 (hours). Counts the time the AC unit is in “On” state. AC unit Alarm Status 10 11 R ▪ ▪ 0: No alarm condition 1: Alarm condition Error Code 6 11 12 R ▪ ▪ ▪ 22 23 R/W 0: No error present 65535(-1 if it is read as signed value): Error in the communication of INMBSFGL001I000 or Remote Controller with the AC unit.
Intesis® Modbus RTU – Fujitsu Register Address (protocol address) Register Address (PLC address) User Manual r1.3 EN R/W Description 0x8000: No temperature’s value is being provided from an external sensor. No virtual temperature is being applied.
Intesis® Modbus RTU – Fujitsu o o o User Manual r1.3 EN This configuration is done via a Fujitsu remote controller connected to the indoor unit (Function number “42” – setting value “1” / operation of Thermosensor button) and must be done by Fujitsu authorized installers at the time of the installation of the AC. Register value after INMBSFGL001I000 startup is -32768, which means that no temperature reference is provided to the AC indoor unit.
Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN DIP-switch Configuration Interface All the configuration values on INMBSFGL001I000 can be written and read from Modbus interface. Otherwise, some of them can also be setup from its on-board DIP-switch interface.
Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN SW2 – Modbus Slave address + Degrees/tenths of degrees (x10) + Temp. magnitude (ºC/ºF) Add SW2-P1..6 Add ON SW2-P1..
Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN SW3 – Termination resistor + BUS polarization configuration SW3-P1..3 Description ON EIA-485 bus without termination resistor (Default value). ON Internal termination resistor of 120Ω connected to EIA-485 bus. ON No BUS polarization (default value). ON BUS polarization active. Table 4.
Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN EIA-485 bus. Termination resistors and Fail-Safe Biasing mechanism EIA-485 bus requires a 120Ω terminator resistor at each end of the bus to avoid signal reflections. To prevent fail status detected by the receivers, which are “listening” the bus, when all the transmitters’ outputs are in three-state (high impedance), it is also required a fail-safe biasing mechanism.
Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN 5 Mechanical & electrical characteristics Enclosure Plastic, type PC (UL 94 V-0) Net dimensions (dxwxh): 93 x 53 x 58 mm / 3.7” x 2.1” x 2.3” Color: Light Grey. RAL 7035 Operation Temperature 0ºC to +70ºC Weight 85 g. Stock Temperature -20ºC to +85ºC Mounting Wall DIN rail EN60715 TH35.
Intesis® Modbus RTU – Fujitsu User Manual r1.3 EN 6 AC Unit Types compatibility Please, check compatibility list at to know which Fujitsu units are compatible with our gateway. https://www.intesis.com/docs/compatibilities/inxxxfgl001i000_compatibility © HMS Industrial Networks S.L.U - All rights reserved This information is subject to change without notice URL https://www.intesis.
Intesis® Modbus RTU – Fujitsu User Manual r1.
Intesis® Modbus RTU – Fujitsu 45 Error in Remote Controller 2d 46 2E 47 48 49 50 51 52 53 54 55 56 117 118 119 120 121 122 123 133 134 135 136 137 138 139 140 141 149 150 151 152 153 154 155 156 157 158 165 166 167 168 169 170 171 172 173 181 182 183 184 185 186 187 188 189 2F 30 31 32 33 34 35 36 37 38 11 12 13 14 15 16 17 21 22 23 24 25 26 27 28 29 31 32 33 34 35 36 37 38 39 3A 41 42 43 44 45 46 47 48 49 51 52 53 54 55 56 57 58 59 Error Code Modbus System User Manual r1.
Intesis® Modbus RTU – Fujitsu Error Code Modbus 195 197 198 199 200 201 202 203 204 205 206 213 214 215 216 217 218 219 220 229 230 231 232 233 234 235 245 246 247 248 249 250 251 252 253 254 259 261 262 263 264 265 266 267 268 269 270 271 272 273 277 278 279 280 281 282 283 Error in Remote Controller 5U 61 62 63 64 65 66 67 68 69 6A 71 72 73 74 75 76 77 78 81 82 83 84 85 86 87 91 92 93 94 95 96 97 98 99 9A 9U A1 A2 A3 A4 A5 A6 A7 A8 A9 AA AC AF AJ C1 C2 C3 C4 C5 C6 C7 System User Manual r1.
Intesis® Modbus RTU – Fujitsu Error Code Modbus 284 285 286 287 288 289 293 294 295 296 309 310 311 312 313 Error in Remote Controller C8 C9 CA CC CF CJ F1 F2 F3 F4 J1 J2 J3 J4 J5 System User Manual r1.