2 Connection
The interface comes with cable + connectors for direct connection to the AC indoor unit, and with a plug-in terminal
block of 3 poles for connection to a Modbus RTU EIA-485 network.
Connect to the AC indoor unit
The INMBSFGL001I000 connects directly to the indoor unit internal control board. In the control board locate the
socket connector marked as CN65.
Figure 2.1 INMBSFGL001I000 connection diagram
Connection to the EIA-485 bus
Connect the EIA-485 bus wires to the plug-in terminal block of INMBSFGL001I000 and keep the polarity on this
connection (A+ and B-). Make sure that the maximum distance to the bus is 1,200 meters (3,937 ft). Loop or star
typologies are not allowed in the case of the EIA-485 bus. A terminator resistor of 120 must be present at each end
of the bus to avoid signal reflections. The bus needs a fail-safe biasing mechanism.