3.3 DIP-switch Configuration Interface
All the configuration values on INMBSMIT001I000 can be written and read from Modbus
interface. Otherwise, some of them can also be setup from its on-board DIP-switch interface.
The device has DIP-switches SW1, SW3
and SW4 on the following locations:
The following tables apply to the interface´s configuration through DIP-switches:
SW1 AC indoor unit’s features: fan speed & vanes
SW1-P1..4
Description
Unidad interior de A.A. con 4 vel. De ventilación y AUTO (Valor por defecto)
AC indoor Unit has 4 fan speeds and AUTO (Default value)
Unidad interior de A.A. con 4 vel. De ventilación
AC indoor Unit has 4 fan speeds
Unidad interior de A.A. con 3 vel. De ventilación y AUTO (Valor por defecto)
AC indoor Unit has 3 fan speeds and AUTO (Default value)
Unidad interior de A.A. con 3 vel. De ventilación
AC indoor Unit has 3 fan speeds
Not defined
Unidad Interior de A.A. con 2 vel. De ventilación
AC Indoor Unit has 2 fan speeds
Not defined
Not defined
AC Indoor Unit has 3 or 4 fan speeds, with or without fan-auto (Default value).
AC Indoor Unit has 2 fan speeds, without fan-auto