3. Modbus Interface Specification
3.1 Modbus physical layer
INMBSMIT001I000 implements a Modbus RTU (Slave) interface, to be connected to an EIA-485
line. It performs 8N2 communication (8 data bits, no parity and 2 stop bit) with several
available baud rates (2400 bps, 4800 bps, 9600 bps -default-, 19200 bps, 38400 bps, 57600
bps, 76800 bps and 115200 bps). It also supports 8N1 communication (8 data bits, no parity
and 1 stop bit).
3.2 Modbus Registers
All registers are type “16-bit unsigned Holding Register” and they use the standard Modbus big
endian notation.
3.2.1 Control and status registers
Register Address
(protocol address)
Register Address
(PLC address)
R/W
Description
0
1
R/W
AC unit On/Off
0:Off
1:On
1
2
R/W
AC unit Mode
1
0:Auto
1:Heat
2:Dry
3:Fan
4:Cool
2
3
R/W
AC unit Fan Speed
1
0:Auto
1:Low
2:Mid-1
3:Mid-2
4:High
3
4
R/W
AC unit Vane Position
1
0:Auto
1:Horizontal
2:Position-2
3:Position-3
4:Position-4
5: Vertical
10: Swing
4
5
R/W
AC unit Temperature Setpoint
1,2,3
-32678 (Initialization value)
16..32ºC (ºC/x10ºC)
61..90ºF
5
6
R
AC unit Temperature reference
1,2,3
-32678 (Initialization value)
10..38ºC (ºC/x10ºC)
50..100ºF
1
Available values will depend on the AC unit mode. Check the AC unit model functions in its Users Manual to know the possible values
for this register.
2
Magnitude for this register can be adjusted to Celsius x 1ºC, Celsius x 10ºC (Default) or Fahrenheit. See section 3.2.3 for more
information
3
It is not possible turn to x10 the value shown in Fahrenheit.