Register Address
(protocol address)
Register Address
(PLC address)
R/W
Description
26
27
R/W
AC unit Horizontal Vane Position
1
0: Auto
1: Horizontal
2: Position-2
3: Position-3
4: Position-4
5: Vertical
37
38
R
Auto mode
0: Auto (Default value)
1: Heat
2: Dry
3: Fan
4: Cool
38
39
R/W
Powerful
0: Off (Default value)
1: On
39
40
R/W
Quiet
0: Off (Default value)
1: On
53
54
R
Compressor Status
0: Off (Default value)
1: To off
2: To on
3: On
54
55
R/W
Compressor On Time
5
0..65535 (hours)
55
56
R/W
Under voltage Count
0..300
56
57
R/W
Heat 8/10 ºC Mode
1,8
0: Off (Default value)
1: On
57
58
R/W
ECO Mode
4
0: Off (Default value)
1: ECONAVI
Auto Comfort
58
59
R
Demand Response (DRM level)
4
0: Normal (Default value)
1: Comp OFF (DRM1)
2: 50% (DRM2)
3: 75% (DRM3)
59
60
R
Human Activity
4
0: Exist (Default value)
1: Not Exist
60
61
R
Outdoor intake temperature
1,2,3,4
-32768: (initialization value) No
temperature’s value is being provided from
an external sensor.
Any other: (ºC/x10ºC/ºF)
61
62
R
Power Consumption
4,9
Value expressed in W
62
63
R
Operation Current
4,9
Value expressed in mA
8
When the value is 1 means that the value goes between 5ºC and 8ºC.
9
The reading of this register equals to the consumption of the full AC system, not the consumption from one single unit.