Instructions

Intesis
TM
INMBSPAN001I100
User’s Manual r1.2 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
Register Address
(protocol address)
Register Address
(PLC address)
R/W
Description
63
64
R
Power Consumption (Slow)
4,9
Value expressed in W. The frequency of the
updates is lower than the one of register 61
(62 PLC)
65
66
R
Input reference temperature
4
-32768: (initialization value) No
temperature’s value is being provided from
an external sensor.
Any other: (ºC/x10ºC/ºF)
66
67
R
Return path temperature
1,2,3
Temperature on the air return of the AC unit
(ºC/x10ºC/ºF).
72
73
R
Today Energy MSW
4,10
0..65535 (hours). Value expressed in Watt-
hour (Energy consumption throughout the
day).
73
74
R
Today Energy lsw
4,10
0..65535 (hours). Value expressed in Watt-
hour (Energy consumption throughout the
day).
74
75
R
Yesterday Energy MSW
4,10
0..65535 (hours). Value expressed in Watt-
hour (Energy consumption throughout the
previous day).
75
76
R
Yesterday Energy lsw
4,10
0..65535 (hours). Value expressed in Watt-
hour (Energy consumption throughout the
previous day).
76
77
R/W
Total Energy MSW
4,10
0..65535 (hours). Value expressed in Watt-
hour
77
78
R/W
Total Energy lsw
4,10
0..65535 (hours). Value expressed in Watt-
hour
97
98
R/W
Block Periodic Sendings
11,12
0: Non-blocked (Default value)
1: Blocked
10
MSW is related to the concept Most Significant word and lsw is related to the concept Least Significant word.
11
If the register is configured as “0:Non-blocked”, all commands received from Modbus will be sent to the AC system. If “1: Blocked”, all
commands received from Modbus will be sent to the AC system if they differ from the previous value.
12
This register applies to firmware version 2.3 onwards