8249
H39
Abnormal indoor
operating unit or standby
units
3 times happen
within 40 minutes
Wrong wiring and
connecting pipe, expansion
valve abnormality, indoor
heat exchanger sensor
open circuit
Check indoor/outdoor connection
wire and connection pipe
Indoor heat exchanger sensor
lead wire and connector
Expansion valve and lead wire
and connector
8257
H41
Abnormal wiring or piping
connection
Wrong wiring and
connecting pipe, expansion
valve abnormality
Check indoor/outdoor connection
wire and connection pipe
Expansion valve and lead wire
and connector.
8280
H58
Indoor gas sensor
abnormality
Continuous for 6
hours
Indoor gas sensor open or
short circuit
Indoor gas sensor
Indoor PCB
8281
H59
ECO patrol sensor
abnormality
Continuous for
70s
ECO patrol sensor open or
short circuit
ECO patrol sensor
ECO patrol and Indoor PCB
8292
H64
Outdoor high pressure
sensor abnormality
Continuous for 1
minutes
High pressure sensor open
circuit during compressor
stop
High pressure sensor
Lead wire and connector
8343
H97
Outdoor fan motor
mechanism lock
2 times happen
within 30 minutes
Outdoor fan motor lock or
feedback abnormal
Outdoor fan motor lead wire and
connector
Fan motor lock or block
8344
H98
Indoor high pressure
protection
Indoor high pressure
protection (Heating)
Check indoor heat exchanger
Air filter dirty
Air circulation short circuit
8345
H99
Indoor operating unit
freeze protection
Indoor freeze protection
(Cooling)
Check indoor heat exchanger
Air filter dirty
Air circulation short circuit
12305
F11
4-way valve switching
abnormality
4 times happen
within 30 minutes
4-way valve switching
abnormal
4-way valve
Lead wire and connector.
12311
F17
Indoor standby units
freezing abnormality
3 times happen
within 40 minutes
Wrong wiring and
connecting pipe, expansion
valve leakage, indoor heat
exchanger sensor open
circuit
Check indoor/outdoor connection
wire and pipe
Indoor heat exchanger sensor
lead wire and connector
Expansion valve lead wire and
connector.
12432
F90
Power factor correction
(PFC) circuit protection
4 times happen
within 10 minutes
Power factor correction
circuit abnormal
Outdoor PCB faulty
12433
F91
Refrigeration cycle
abnormality
2 times happen
within 20 minutes
Refrigeration cycle
abnormal
Insufficient refrigerant or valve
close
12435
F93
Compressor abnormal
revolution
4 times happen
within 20 minutes
Compressor abnormal
revolution
Power transistor module faulty or
compressor lock
12436
F94
Compressor discharge
pressure overshoot
protection
4 times happen
within 30 minutes
Compressor discharge
pressure overshoot
Check refrigeration system
12437
F95
Outdoor cooling high
pressure protection
4 times happen
within 20 minutes
Cooling high pressure
protection
Check refrigeration system
Outdoor air circuit
12438
F96
Power transistor
module
overheating protection
4 times happen
within 30 minutes
Power transistor module
overheat
PCB faulty
Outdoor air circuit (fan motor)
12439
F97
Compressor overheating
protection
3 times happen
within 30 minutes
Compressor overheat
Insufficient refrigerant
12440
F98
Total running current
protection
3 times happen
within 20 minutes
Total current protection
Check refrigeration system
Power source or compressor lock
12441
F99
Outdoor direct current
(DC) peak detection
Continuous
happen for 7 times
Power transistor module
current protection
Power transistor module faulty or
compressor lock
In case to detect an error code not listed, contact your closest Panasonic technical support