Instructions

Intesis
TM
INMBSPAN001I100
User’s Manual r1.2 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
Register Address
(protocol address)
Register Address
(PLC address)
R/W
Description
5
6
R
AC unit Temperature reference
1,2,3,4
-32768 (Initialization value)
10..42ºC (ºC/x10ºC)
50..108ºF
6
7
R/W
Window Contact
0: Closed (Default value)
1: Open
7
8
R/W
INMBSPAN001I100 Disablement
5
0: INMBSPAN001I100 enabled (Default)
1: INMBSPAN001I100 disabled
8
9
R/W
AC Remote Control Disablement
5
0: Remote control enabled (Default)
1: Remote control disabled
9
10
R/W
AC unit Operation Time
5
0..65535 (hours). Counts the time the AC
unit is in “On” state.
10
11
R
AC unit Alarm Status
0: No alarm condition
1: Alarm condition
11
12
R
Error Code
6
0: No error present
65535 (-1 if read as a signed value): Error in
the communication of INMBSPAN001I100
with the AC unit.
Any other error present, see the table at the
end of this document.
22
23
R/W
Indoor unit´s ambient temperature from
external sensor (at Modbus side)
1,2,3,7
-32768: (Initialization value). No
temperature is being provided from an
external sensor.
Any other: (ºC/x10ºC/ºF)
23
24
R
AC Real temperature setpoint
1,2,3,7
When no external temperature is provided,
this read-only register will have the same
value as register 5 (PLC addressing). In all
cases, it will show the current setpoint in the
indoor unit.
16..31ºC (ºC/x10ºC)
60..92ºF
24
25
R
Current AC max. setpoint
1,2,3
-32768 (Initialization value)
30ºC (ºC/x10ºC)
86ºF
25
26
R
Current AC min. setpoint
1,2,3
-32768 (Initialization value)
16ºC C/x10ºC)
61ºF
4
Feature only available on 2013 models (PKE series) and onwards.
5
This value is stored in non-volatile memory
6
See section 7 for possible error codes and their explanation
7
See section 4.2.3 for more information