Functionality
After the start up process, Intesis helps route Modbus communications from a Modbus TCP to Modbus RTU
networks, allowing Modbus TCP devices to cummunicate with Modbus RTU devices present in another network.
It is not necessary to perfom any mapping as the data from one side is shown on the other side in a transparent way.
The router also has diagnostic signals available trough TCP port 503 to check that all the communication from each
side is working properly.
Router capacity
Intesis capacity is listed below:
Element
32 devices
Notes
Type of Modbus
slave devices
Modbus RTU (EIA485)
Modbus TCP
Those supporting Modbus
protocol. Communication over
TCP/IP and RTU
Number of Modbus
slave devices
Up to 32 full-load RTU devices
Number of Modbus slave
devices supported by the device