Instructions

Intesis
TM
INMBSSAM001R000
User’s Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
4. Modbus Interface Specification
4.1 Modbus physical layer
INMBSSAM001R000 implements a Modbus RTU (Slave) interface, to be connected to an EIA-
485 line. It performs 8N2 communication (8 data bits, no parity and 2 stop bit) with several
available baud rates (2400 bps, 4800 bps, 9600 bps -default-, 19200 bps, 38400 bps, 57600
bps, 76800 bps and 115200 bps). It also supports 8N1 communication (8 data bits, no parity
and 1 stop bit).
4.2 Modbus Registers
All registers are type “16-bit unsigned Holding Register” and they use the Modbus big endian
notation.
4.2.1 Control and status registers
Register Address
(protocol address)
Register Address
(PLC address)
R/W
Description
0
1
R/W
AC unit On/Off
0: Off
1: On
1
2
R/W
AC unit Mode
1
0: Auto
1: Heat
2: Dry
3: Fan
4: Cool
2
3
R/W
AC unit Fan Speed
1
0: Auto
1: Low
2: Mid
3: High
3
4
R/W
AC unit Vane Position
1
0: Auto
10: Swing
4
5
R/W
AC unit Temperature setpoint
1,2,3
-32768 (Initialization value)
18..30ºC (ºC/x10ºC)
65..86ºF
5
6
R
AC unit Temperature reference
1,2,3
-32768 (Initialization value)
10..38ºC (ºC/x10ºC)
50..100ºF
6
7
R/W
Window Contact
0: Closed (Default)
1: Open
1
Available values will depend on the AC unit mode. Check the AC unit model functions in its user manual to know the possible values for
this register.
2
Magnitude for this register can be adjusted to Celsius x 1ºC, Celsius x 10ºC (default) or Fahrenheit. See section 4.2.3 for more
information.
3
It is not possible turn to x10 the value shown in Fahrenheit.