Instructions

Intesis
TM
INMBSSAM001R000
User’s Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
Register Address
(protocol address)
Register Address
(PLC address)
R/W
Description
7
8
R/W
INMBSSAM001R000 Disablement
4
0: INMBSSAM001R000 enabled (Default)
1: INMBSSAM001R000 disabled
8
9
R/W
AC Remote Control Disablement
4
0: Remote Controller enabled (Default)
1: Remote Controller disabled
9
10
R/W
AC unit Operation Time
4
0..65535 (hours). Counts the time the AC
unit is in “On” state.
10
11
R
AC unit Alarm Status
0: No alarm condition
1: Alarm condition
11
12
R
Error Code
5
0: No error present
65535(-1 if it is read as signed value): Error
in the communication of INMBSSAM001R000
or Remote Controller with the AC indoor unit.
Any other error present, see the table at the
end of this document.
22
23
R/W
Indoor unit´s ambient temperature from
external sensor (at Modbus side)
1,2,3,6
-32768: (Initialization value). No
temperature is being provided from an
external sensor.
Any other: (ºC/x10ºC/ºF)
23
24
R
AC Real temperature setpoint
1,2,3,6
When no external temperature is provided,
this read-only register will have the same
value as register 5 (PLC addressing). In all
cases, it will show the current setpoint in the
indoor unit.
Ranges determined by the Manufacturer of
the AC indoor unit: (ºC/x10ºC/ºF)
26
27
R/W
AC unit Left/Right Vane Position
0: Auto (Default)
10: Swing
66
67
R
Return path Temperature
1,2,3
-32768 (Initialization value)
Ranges determined by the Manufacturer of
the AC indoor unit: (ºC/x10ºC/ºF)
97
98
R/W
Block Periodic Sendings
4,7,8
0: Non-blocked (Default value)
1: Blocked
98
99
R/W
Master/Slave (gateway)
0: Slave
1: Master
4
This value is stored in non-volatile memory
5
See section 7 for possible error codes and their explanation
6
See section 4.2.3 for more information
7
If the register is configured as “0:Non-blocked”, all commands received from Modbus will be sent to the AC system. If “1: Blocked”,
commands from Modbus will only be sent to the AC system if they differ from the previous value (values sent on change).
8
This register applies to firmware version 0.3 onwards.