User's Manual

Table Of Contents
StreetNode™ 6250 PTP
Installation & Cabling Manual - Edition 2.1
9
List of Materials, Continued
Grounding
materials
Grounding cables for indoor and outdoor installation are available depending
on the installation premises requirements.
In each case, two wire gauges are available:
16mm
2
cable is used for units installed on structures where lightning strike
is possible (rooftop, telecommunication towers etc.).
6mm
2
cable is used for units installed in structures and locations where
lightning strike is not considered possible.
The following table shows the grounding materials:
Item Order Code / Photo Description
A
GND-KIT16-OD
Grounding kit of StreetNode
TM
6250 PTP radio
unit:
No Description
1
16 mm
2
cable, stranded, green / yellow, 450 V,
(2 m).
2
M8 screws (2), nuts (2), washers (2), lock
washers (6) & tie wrap.
3 M8 Ring Terminal.
4 M5 Ring Terminal.
5
Heat shrinkable tube, black, d= 9.5 mm / 4.8
mm.
6 Terminal pin, AWG6, non insulated.
B
GND-CAB6-ID
Indoor grounding cable, 6 mm
2
, stranded,
green / yellow, 450 V (per meter).
C
GND-CAB6-OD
Outdoor grounding cable, 6 mm
2
, stranded,
BLK, UV-rated, 0.6 / 1 kV (per meter).
D
GND-CAB16-ID
Indoor grounding cable, 16 mm
2
, stranded,
green / yellow, 450 V (per meter).
E
GND-CAB16-OD
Outdoor grounding cable, 16 mm
2
, stranded,
BLK, UV-rated, 0.6 / 1 kV (per meter).
Continued on next page