6. Installation and use procedures
9. "Connect the control unit to the sensors" on page57.
Note: connect the sensors to the control unit off-site if access to the connectors becomes difficult once they
are installed.
10. "Assign the Node IDs" on page57
11. "Save and print the configuration" on page58.
12. If available, "Set the control unit Ethernet parameters" on page58
13. "Validate the safety functions" on page59.
6.2 Install and configure SBV System Series
6.2.1 Install the control unit
WARNING! To prevent tampering, make sure the control unit is only accessible to authorized
personnel (e.g. key-locked electrical panel).
1. Mount the control unit on the DIN rail.
2. Make electrical connections, see "Terminal blocks and connector pin-outs" on page82 and "Electrical
connections" on page84.
NOTICE: if at least one input is connected, the SNS input "V+ (SNS)" and the GND input "V- (SNS)" must also
be connected.
NOTICE: when powered, the system takes about 20 s to start. During that period the outputs and the
diagnostic functions are deactivated and the green sensor status LEDs of the connected sensors flash.
Note: to correctly connect the digital inputs, see "Voltage and current limits for digital inputs" on page82.
6.2.2 Synchronize the control units
If there are more than one control unit in the area, perform the following steps:
1. In the Inxpect Safety application, click Settings > Multi-control unit synchronization.
2. Assign a different Control unit channel to each control unit.
Note: if there are more than four control units, the control units with the same channel must have their
monitored areas as far from each other as possible.
6.2.3 Define the area to be monitored
WARNING! The system is disabled during configuration. Prepare opportune safety measures in the
dangerous area protected by the system before configuring the system.
1. In the Inxpect Safety application, click Configuration.
2. Add the desired number of sensors in the plane.
3. Define the position and inclination of each sensor.
4. Define the selected safety working modes, the detection distance, the angular coverage and the restart
timeout for each detection field of each sensor.
6.2.4 Configure the inputs and outputs
1. In the Inxpect Safety application, click Settings.
2. Click Digital Input-Output and define the input and output functions.
3. If the muting is managed, click Muting and assign the sensors to the groups according to the logic of the
digital inputs.
4. Click APPLY CHANGES to save the configuration.