Instruction Manual
Table Of Contents
- Glossary of terms
- 1. This manual
- 2. Safety
- 3. Get to know SBV System Series
- 4. Functioning principles
- 4.1 Sensor functioning principles
- 4.2 Detection fields
- 4.3 Safety working modes and safety functions
- 4.4 Safety working mode: Both (default)
- 4.5 Safety working mode: Always access detection
- 4.6 Safety working mode: Always restart prevention
- 4.7 Restart prevention function: static object detection option
- 4.8 Features of the restart prevention function
- 4.9 Muting
- 4.10 Anti-tampering functions: anti-rotation around axes
- 4.11 Anti-tampering functions: anti-masking
- 5. Sensor position
- 6. Installation and use procedures
- 7. Maintenance and troubleshooting
- 8. Technical references
- 9. Appendix
60
SBV System Series| Instruction manual v1.2 DEC 2021 |SAF-UM-SBVBus-en-v1.2|© 2021 Inxpect SpA
6. Installation and use procedures
6.3.3 Example of access points
Access points for 100° field of view
6.3.4 Validate the restart prevention function
Example 1
Starting conditions l Detection field dependency: Dependent mode
l Machinery in safe conditions
l Two detection fields configured (detection field 1 and detection field 2)
l Both the safety outputs (detection signal 1 and detection signal 2) deactivated
Validation
procedure
1. Stand still in detection field 1.
2. Check that the system maintains both related safety outputs deactivated. See
"Validate the system with Inxpect Safety" on the next page.
3. Stand still in detection field 2.
4. Check that the system maintains only the second safety output deactivated. See
"Validate the system with Inxpect Safety" on the next page.
5. If the safety outputs do not remain deactivated, see "Troubleshooting validation" on
the next page.
Specifications l Stop longer than the restart timeout (Inxpect Safety > Configuration).
l Stop in several different points, with special attention to the areas in close proximity to
the sensor and any blind spots, see "Example of stopping points" below.
l Stop standing as well as laid down.
Example 2
Starting conditions l Detection field dependency: Independent mode
l Machinery in safe conditions
l Two detection fields configured (detection field 1 and detection field 2)
l Both the safety outputs (detection signal 1 and detection signal 2) deactivated
Validation
procedure
1. Stand still in detection field 1.
2. Check that the system maintains only the specific safety output deactivated. See
"Validate the system with Inxpect Safety" on the next page.
3. Repeat step 1 and 2 for detection field 2.
4. If the safety outputs do not remain deactivated, see "Troubleshooting validation" on
the next page.
6.3.5 Example of stopping points
Stopping points for 100° field of view