Controller Manual

Ion Genesis
®
II Pump Controller
Digital Level Control with Pump Alternation
and High Water Alarm
OPERATION MANUAL
Dated: 07/10/2017
Document Name: IonGenesisII_OM
Page 6 of 8
www.ionproducts.net
Figure 2: Duplex Operation – 2 pumps with similar current draw installed; both intended to run simultaneously
when required.
Number
of Pumps
Running
Current
Duplex
Pumping
Locked
Out
*
Duplex
Pumping
Forced
Off
Pump
Alternate
To Next
Pump
Beep
Open
Remote
Alarm
Contacts
LCD
Updates
Locked
Out
*
Bad
2
Extreme X X X X X
High, 3 Times X X X X X
High X X X
Low X X X
1
Critical N/A N/A X X X X X
Extreme, 3 Times N/A N/A X X X X X
Extreme N/A N/A X X X
High, 3 Times N/A N/A X X
High N/A N/A X X
Low N/A N/A X X X X
Figure 3: Duplex Mixed Operation – 2 pumps with dissimilar current draws installed; both intended to run
simultaneously when required.
Number
of Pumps
Running
Current
Duplex
Pumping
Locked
Out
*
Duplex
Pumping
Forced
Off
Pump
Alternate
To Next
Pump
Beep
Open
Remote
Alarm
Contacts
LCD
Updates
Locked
Out
*
Bad
2
Extreme X X X X X
High, 3 Times X X X X X
High X X X
Low X X X
1
Critical N/A N/A X X X X X
High, 3 Times N/A N/A X X X X
High N/A N/A X X X
Low N/A N/A X X X X
Figure 4: Alternating, Simplex Operation – 2 pumps installed, only one pump intended to run at one time.
Number
of Pumps
Running
Current
Pump
Alternate
To Next
Pump
Beep
Open
Remote
Alarm
Contacts
LCD
Updates
Locked
Out
*
Bad
1
Extreme X X X X X
High, 3 Times X X X X X
High X X X X X
Low X X X X