Installation Manual

_____________________________________________________________________________________
303550 Installation Manual E-Series CMU Confidential
Revision Date: 14-Apr-2020 Revision: S
Process Owner: Engineering Page 34 of 36
Cautions
These instructions are not designed to imply or replace any operating or safety rules.
It is the responsibility of the installer to understand and follow all company safety practices.
WARNING In order to comply with hazardous classification, only those items
specifically listed can be used and must be used only as shown. Substitution of components
may affect intrinsic safety.
WARNING Installation shall be carried out in accordance with the applicable code of
practice by suitably trained personnel.
WARNING Repair of this equipment shall be carried out in accordance with the
applicable code of practice.
WARNING Any machining, drilling, and/or sanding related to the installation of this
system should be pre-approved by the authorized department before work is started.
WARNING If the equipment is likely to come into contact with aggressive substances,
then it is the responsibility of the user to take suitable precautions that prevent it from being
adversely affected, thus ensuring that the type of protection is not compromised.
WARNING RF Device: Unit cannot be painted or coated with any material. Coating can
adversely affect the performance of the device. Unit shall be masked appropriately if post
installation coating is required.
WARNING EXPLOSION HAZARD: The equipment temperature Class is T4 and only
certified for use in ambient temperatures. Product is rated from -40 C to +55 C and should not
be used outside this range in an explosive environment.
WARNING POTENTIAL ELECTROSTATIC CHARGING HAZARD: Under certain extreme
circumstances, the non-metallic parts incorporated in the enclosure of this equipment may
generate an ignition-capable level of electrostatic charge. Therefore, the equipment shall not be
installed in a location where the external conditions are conducive to the build-up of electrostatic
charge on such surfaces. This is particularly important if the equipment is installed in a zone 0
location.
WARNING POTENTIAL ELECTROSTATIC CHARGING HAZARD: Suitable for hose down
cleaning only. Do not clean unit with a dry cloth. Static can be generated when two dry parts are
rubbed together.
WARNING DO NOT OPEN WHEN EXPLOSIVE ATMOSPHERE IS PRESENT. Battery
replacement shall be done in an area known to be non-hazardous. Use only replaceable battery
pack ADS model 303382 (19 mAH) or 303406 (76 mAH). See battery replacement procedure in
Appendix E.
WARNING Products contain Primary Lithium batteries. Proper disposal procedures are
required at end of life conditions. Use local regulatory disposal method for lithium Thionyl
chloride batteries. For example, disposal procedure 49 CFR 173.185 or Directive 2006/66/CE.