Iota Technical Paper - Charging Lead Acid Batteries for Long Life

Charging Flooded Lead Acid Batteries
for Long Battery Life
How to Prevent Sulfation and
Excessive Gassing That Ruin 12V-48V
Flooded Lead Acid Batteries
From the
IOTA Power Products
Technical Library
Content Highlights
Battery owners expect optimal performance from their batteries, but don’t
always know the best practices to get long life and reliability from them. With
some understanding of cause, effect and prevention of leading causes of prema-
ture battery failure, owners can expect more years of safe and reliable opera-
tion from their batteries.
Two leading causes of capacity loss, failure, and hazards in ooded lead acid
batteries are sulfation and excessive gassing. Both of these can be largely pre-
vented by using smart charging technology to safely store these types of batter-
ies at full charge.
Sulfation, Undercharging, and Battery Failure
The leading cause of battery failure is sulfation. Sulfation is a deposit of lead
sulfate crystals on the charging plates that resists the battery’s ability to ac-
cept a charge. Eventually, the deposits will prohibit charging, reducing both the
battery’s capacity and functional life. The source of the sulfate is the water and
sulfuric acid electrolyte solution inside the battery. An ongoing electrochemical
reaction between opposite charges occurs in the electrolyte solution that pro-
duces electrons. These reactions are at their optimal state while the battery is at
the correct full charge, but are diminished when the battery is undercharged or
overcharged.
During normal charge and discharge some minor sulfation occurs, but major sulfa-
tion can develop when the battery is stored in an uncharged or undercharged
condition, which eventually slows and stops the electrochemical reactions. If these
reactions stop, sulfation is accelerated as the sulfur leaches out of the electrolyte
solution and attaches itself to the lead charging plates. As more crystals deposit on
the charging plate, the ability for the battery to accept full charge diminishes, and
undercharging worsens. This is a downward spiral to premature battery failure.
Two leading causes
of battery failure are
sulfation and excessive
gassing.
Good management
and correct charging
greatly improve battery
performance.
Multi-stage charging
technology, such as
IOTAs IQ4 Smart
Charger, is the safest
and most effective
method of charging
ooded lead acid
batteries.
How smart charging
technology prevents
sulfation and exces-
sive gassing.

Summary of content (4 pages)