INSTALLATION INSTRUCTIONS
CAUTION: Before installing, make certain the A.C. power is off and the ILB unit
connector is disconnected.
1. LED LIGHT
The ILB can be used with most LED loads that operate at 24VDC or 12VDC. See the ILB Model Specification
Chart for output specifications of the unit being installed.
2. MOUNTING THE ILB
Mount the ILB in the driver/lamp compartment or enclosed wireway so the wire leads are not exposed, at least ½″
away from the driver. Refer to Illustration 1. For mounting the ILB on top of the fixture, use the optional TMK-80
mounting accessory for covering the wires that enter the fixture. Refer to Illustration 2.
When battery packs are remote mounted, consult Customer Service for the maximum allowable distance between
the battery pack and the load.
3. WIRING
Refer to the wiring diagram on the back page for the appropriate wiring of the LED load and driver. Install in ac-
cordance with the National Electrical Code and local regulations. For additional wiring diagrams consult Cus-
tomer Service.
4. INSTALLING THE CHARGE INDICATOR
Select a convenient location on the fixture so that the Charge Indicator can be seen after installation. Allow for
proper clearance and drill or punch a
1
/
2
″ mounting hole. Disconnect the leads from the Charge Indicator. Push
the Charge Indicator into the
1
/
2
″ hole until it is firmly locked into place. Reconnect the leads, observing proper
polarity (Red/Black or Red lead w/connector to positive (+) red tab). Make certain all leads are enclosed in an ap-
propriate wireway. Refer to Illustrations 1 and 2.
5. INSTALLING THE TEST SWITCH
The Test Switch should be mounted on the fixture to allow access to authorized personnel. Drill or punch a ½″
mounting hole. Make certain all leads are enclosed in an appropriate wireway. Refer to Illustrations 1 and 2.
Illustration 1
ILB-1207
ILB-1212
ILB-2407
ILB-2412
12VDC
12VDC
24VDC
24VDC
7
12
7
12
*ALL VOLTAGES AND WATTAGES ARE NOMINAL
ILB MODEL SPECIFICATION CHART
NOTE: Position the Charge Indicator and Test
Switch so that they are accessible after installation.
7/8” BUSHING
DRIVER
COMPARTMENT
CHARGE INDICATOR
CEILING
TILE
7/8” BUSHING
DRIVER
COMPARTMENT
CEILING
TILE
TMK-80
TEST SWITCH
CHARGE INDICA
TOR
TEST SWITCH
Illustration 2
ILB
ILB