3" Top Caps Manual

GROUND MOUNT INSTALLATION MANUAL - 12© 2019 IRONRIDGE, INC. VERSION 2.8
MICROINVERTER KITS
One Microinverter
Kit Required
(80 in-lbs)
Use IronRidge's Microinverter Kit to bond compatible
microinverters and power optimizers to the racking system.
Insert Microinverter Kit T-bolt into top rail slot. Place
compatible microinverter or power optimizer into position
and tighten hex nut to 80 in-lbs.
If installing in areas with ground snow loads greater than 40 psf,
install MLPE devices directly next to module frame edge
SYST
EMS USING
ENPHASE
MICROINVERTERS OR SUNPOWER AC MOD-

installed equipment grounding conductors (EGC). This solution meets the requirements of UL 2703 for bonding and
grounding and is included in this listing.
COMPATIBLE PRODUCTS
Sunpower
Modules with model identier Ab-xxx-YY and InvisiMount (G5) 46mm frame; where “A” is either E, or X; “b” can be 17, 18, 19, 20, 21, or 22;
and “YY” can be C-AC, D-AC, BLK-C-AC, or BLK-D-AC.
Enphase
Microinverters M250-72, M250-60, M215-60, C250-72, and Engage cables ETXX-240, ETXX-208, ETXX-277.
A minimum of two inverters mounted to the same rail and connected to the same Engage cable are required.
The microinverters or Sunpower AC modules must be used with a maximum 20 A branch rated overcurrent protection device (OCPD).
If an AC module is removed from a circuit for maintenance, you must rst disconnect AC power and then install a temporary EGC to
bridge the gap by inserting an AC extension cable (or via other NEC-compliant means), in order to maintain e󰀨ective ground continuity
to subsequent modules.
On AP systems equipment,
remove Grounding Washer
#
COMPATIBLE PRODUCTS
Enphase
M250-72, 250-60, M215-60, C250-72, S230, S280, IQ 6, IQ 6+, IQ
IQ7, IQ 7A, IQ 7+, IQ 7X, Q Aggregator
Darfon
MIG240, MIG300, G320, G640
Solar Edge
M1600, P300, P320, P340, P370, P400, P401, P405, P485, P505,
P600, P700, P730, P800p, P800s, P801, P850, P860, P950, P960
SMA
RoofCommKit-P2-US, TS4-R Module Retrot Kits (TS4-R-S,
TS4-R-O, TS4-R-F)
Tigo
Tigo Access Point (TAP)
TS4-R-X (where X can be F, M, O, or S)
TS4-R-X-DUO (where X can be M, O, or S)
TS4-A-X (where X can be F, 2F, O, O-DUO, or S)
AP Systems
QS1, YC600
Remove Grounding Washer on AP Systems QS1 and YC600
inverters before installing to XR rails.
Remove the Stainless Steel Clip on Tigo-”A” MLPE Devices
before attaching to XR rails.
Use the number of IronRidge Microinverter kits allowed
by the MLPE mounting ange. Some will require 1 kit and
others 2 kits.
Two Microinverter
Kits Required
(80 in-lbs)