Ground Mount Installation Guide

GROUND MOUNT INSTALLATION MANUAL - 12©
2019 IRONRIDGE, INC. VERSION 2.1
FRAMELESS MODULE KITS
Place
Star Washer
Module Clamp
(80 in-lbs)
One Grounding Lug Per
Continuous Subarray
Insert Frameless Kit T-bolt in top rail slot. Place star
washer over T-bolt, allowing it to rest on top of rail. Secure
module clamps with a hex nut and torque to 80 in-lbs.
Þ Tested or evaluated module clamps:
Sunforson silver or black SFS-UTMC-200(B) mid and SFS-
UTEC-200(B) end clamps.
Sunpreme silver or black mid and end clamps with part
numbers 7500105X where X can be 1, 5, 6 or 7.
IronRidge silver or black mid and end clamps with part
numbers FMLS-XC-001-Y where X can be “E” or “M” and Y can
be “B” or blank.
Þ Follow module manufacturers installation instructions to install
the module clamps.
Þ Frameless modules require using a Grounding Lug on every rail.
Þ For Sunpreme Modules Only: If required to use slide prevention
hardware, see Module Slide Prevention Addendum (Version 1.10).
MODULE COMPATIBILITY
The Ground Mount System may be used to ground and/or mount a PV module complying with UL 1703 only when the
specic module has been evaluated for grounding and/or mounting in compliance with the included instructions. Unless
otherwise noted, “xxx” refers to the module power rating and both black and silver frames are included in the certication.
MAKE
MODELS
Amerisolar
Amerisolar modules with 35, 40 and 50 mm frames AS-bYxxxZ Where "b" can be 5 or 6; "Y" can be M,
P, M27, P27, M30, or P30; "xxx" is the module power rating; and "Z" can be blank, W or WB
Astronergy Solar
Astronergy modules with 30, 35, 40 and 45 mm frames aaSMbbyyC/zz-xxx Where “aa” can be CH or
A; "bb" can be 60, 66, or 72; “yy” can be blank, 10 or 12; "C" can M, P, M(BL), M-HC, M(BL)-HC, P-HC,
(DG), or (DGT); “zz” can be blank, HV, F-B, or F-BH ; and “xxx” is the module power rating
Astronergy frameless modules CHSM6610P(DG)-xxx Where “xxx” is the module power rating
Auxin
Auxin modules with 40 mm frames AXN6y6zAxxx Where "y" can be M or P; "z" can be 08, 09, 10, 11, or
12; "A" can be F or T; and "xxx" is the module power rating
Axitec
Axitec Modules with 35 and 40 mm frames AC-xxxY/aaZZb Where "xxx" is the module power rating; "Y"
can be M, P or MH; "aa" can be blank, 125- or 156-; "ZZ" can be 54, 60, 72, 120, or 144; "b" can be S or
SB
Boviet
Boviet modules with 40mm frames BVM66aaYY-xxx Where "aa" can be 9, 10 or 12; "YY" is M or P; and
"xxx" is the module power rating
BYD
Where "xxx" is the module power rating; "Y" can be M, P or MH; "aa" can be blank, 125- or 156-; "ZZ"
can be 54, 60, 72, 120, or 144; "b" can be S or SB
Canadian Solar
Canadian Solar modules with 30, 35 and 40 mm frames CSbY-xxxZ Where "b" can be 1, 3 or 6; "Y" can
be H, K, P, U, V, W, or X; "xxx" refers to the module power rating; and "Z" can be M, P, MS, PX , M-SD,
P-AG, P-SD, MB-AG, PB-AG, MS-AG, or MS-SD
Canadian Solar frameless modules CSbY-xxx-Z Where "b" can be 3 or 6; "Y" is K, P, U, or X; "xxx" is the
module power rating, and "Z" can be M-FG, MS-FG, P-FG, MB-FG, or PB-FG
CertainTeed
CertainTeed modules with 35 and 40 frames CTxxxYZZ-AA Where "xxx" is the module power rating; "Y"
can be M, P or HC; "ZZ" can be 00,01, 10, or 11; and "AA" can be 01, 02, 03 or 04
CSUN
Csun modules with 35 and 40 mm frames YYxxx-zzAbb Where "YY" is CSUN or SST; xxx is the module
power rating; "zz" is blank, 60, or 72; and "A" is blank, P or M; "bb" is blank, BB, BW, or ROOF
Ecosolargy
Ecosolargy modules with 35, 40 and 50 mm frames ECOxxxYzzA-bbD Where "xxx" is the module power
rating; "Y" can be A, H, S, or T; "zz" can be 125 or 156; "A" can be M or P; "bb" can be 60 or 72; and "D"
can be blank or B