B. Heat Pump WITHOUT back-up electric heat
e reversing valve, the compressor, the outdoor con-
denser fan motor and the indoor fan motor shall be
energized. Reverse cycle heating shall occur when the
outdoor temperatures are 35 °F and above.
If outdoor coil temperature drops below 28 °F or
the outdoor air temperature drops to 35 °F or less,
the compressor stops and there is no source of heat.
When the outdoor coil temperature rises back to
40 °F or above, the compressor reverse cycle is the
heat source.
A temperature-sensing device shall be used to moni-
tor the outdoor coil temperature to limit frost buildup.
Defrosting of the outdoor coil will be activated when
outdoor coil temperature drops below 28 °F of out-
door air temperature drops to 35 °F or less. Defrost-
ing is terminated when outdoor coil temperature rises
back to 40 °F. During defrosting, both compressor
and the outdoor fan are turned o.
e indoor fan will stop if indoor coil temperature
falls below 78 °F. It will restart at its set speed when
indoor coil temperature rises back to 80 °F.
4.01 ACCESSORIES:
A. Metal Wall Sleeve shall be a one-piece, extended wall
sleeve, with factory installed insulation.
B. Architectural louver shall be painted aluminum for a
superior color match to the building.
C. Subbase shall be pre-assembled from the factory and
be UL listed.
Subbase options include:
1. Non-electrical subbase: e non-electrical subbase
shall be pre-assembled and provides mechanical sup-
port and requires no wiring.
Performance Specifications (cont.)
2. Electrical subbase: e electrical subbase shall be
pre-assembled with factory-installed electrical junc-
tion box containing a receptacle for corded units.
3. Hardwired subbase: e hardwired electrical sub-
base shall be pre-assembled with factory installed
electrical junction box containing 19 inches of
exible conduit (for a perfect t to the unit) and all
mating connections.
D. Hardwire kit shall provide a permanent
connection
to the unit.
e hardwire kit mounts on the front right side of the
unit and shall have 36 inches of exible steel conduit
and a connector for easy connect/disconnect.
E. Condensate Drain
is universal drain kit shall be used internally or
externally to route excess condensate to a drainage
system. It can be eld-installed on any Islandaire wall
sleeve. e drain kit shall be attached to the exterior
right or le side of the wall sleeve for external drain-
ing or may be mounted to the bottom of the wall
sleeve for internal draining.
F. Lateral Duct:
e kit shall include an adapter plenum, extension
duct, wall register and wall molding. e lateral duct
system allows one system to heat or cool two adjacent
rooms, by directing up to 30% of the airow to the
adjacent room.
G. Power Vent:
is specially designed fan delivers up to approxi-
mately 95 CFM of fresh air through the vent while the
fan is operating.