Connecting and Configuring the Module and Instrument
TDC
-1346-000 100T-HON Honeywell Telemetry Module Installation Guide 16
Proprietary and Confidential
Honeywell Instrument Call-In Configuration
The installer must configure the Honeywell Instrument properly to support the instrument-controlled alarm
call-in feature. Automatic instrument configuration is not supported by the 100T-HON module. Configure the
call-in feature using the following item codes.
Mini-Max
Item Number
Item Description
Set Value
Value Meaning
126 Instrument baud rate 0 9600 Baud
139 Serial link access 0 Full read/write
238 Serial Log Trigger 1 Active
333 Call-in trigger 1 Alarm call-in enabled
336 Call-in retry by 0 Host
405 Call-in delay time 4 4 seconds
486 Modem AT enable 1 call-in using AT commands
491 Modem init-string ATE0Q0V0X4
-
492 Modem dial string ATDT -
493 Alarm call-in phone number 924-9900 -
494 Modem hangup string ATH0 -
495 Modem retry interval A 5 5 minutes
496 Modem retry interval B 1440 1440 minutes
497 Modem retry A count 3 3 retries
821 Modem wake-up delay 50 5 seconds
Mini-AT
Item Number
Item Description
Set Value
Value Meaning
126 Instrument baud rate 0 9600 Baud
139 Serial link access 0 Full read/write
238 Serial Log Trigger 1 Active
333 Call-in trigger 1 Alarm call-in enabled
336 Call-in retry by 0 Host
405 Call-in delay time 4 4 seconds
486 Modem AT enable 1 call-in using AT commands
491 Modem init-string ATE0Q0V0X4
-
492 Modem dial string ATDT -