Connecting and Configuring the Module and Instrument
TDC
-1346-000 100T-HON Honeywell Telemetry Module Installation Guide 18
Proprietary and Confidential
The Mechanical Uncorrected Volume Switch
The 100T-HON telemetry module supports a connection to a mechanical uncorrected volume switch output
from the Honeywell Mini-Max and Mini-AT instruments. This switch output allows the 100T-HON telemetry
module to independently count the mechanically uncorrected volume, even if the instrument losses power.
To collect mechanical uncorrected volume data, the following must be true:
• The instrument must have the mechanical pulse output option board installed.
• The module’s mechanical pulser cable must be connected to the Honeywell instrument.
• The module must be configured to use the mechanical uncorrected volume as its channel 2 data stream.
The 100T-HON telemetry module pulse counter supports a maximum of 1 pulse per second with at least 1/3
second on, and 1/3 second off.
Electronic Corrected Pulse Output
The 100T-HON telemetry module does not provide a connection to an instrument electronic corrected pulse
output. Electronic corrected volume data is collected through the serial connection.
Electronic Uncorrected Pulse Output
The 100T-HON telemetry module does not include a connection to an instrument electronic uncorrected pulse
output. Electronic uncorrected volume data is collected through the serial connection.
Alarm Switch
The 100T-HON telemetry module does not include a connection to an instrument alarm switch. The
instrument alarm data is collected through the serial connection.
Honeywell Instrument Cable Connections
The 100T-HON telemetry module cable enters the Honeywell instrument through a watertight compression
connector on the back of the instrument.
Mini-AT compression connector ERX/MiniMax compression connector
The 100T-HON telemetry module connects to the Honeywell Mini-AT, MiniMax, and ERX instruments.