User's Manual

Initializing, Connecting, and Programming
TDC-0951-001 100W-R and 100WP-R Datalogging Water Endpoint Installation Guide 8
Proprietary and Confidential
Connecting the 100WP-R to a Remote Meter Register
Connect the 100WP-R wires from the endpoint to the register according to the following table.
100WP-R Connections
Register Manufacturer
100WP-R wire color
Brown
(signal)
Gray
(common)
Yellow
(tamper)
Register screw color designator
Elster Digital
BLK
GRN
R
Itron (Actaris) Cyble Sensor (2-
wire)
Either wire
Remaining wire must be connected to both
endpoint wires
Badger RTR
R
BLK
Green/bare
Elster V100
BLK
R
Blue
Sensus PMM
R
BLK
Bare
Connect the endpoint to the cable using gel-cap connectors (see Using Gel Cap Connectors on page 33).
Using an Extension Cable
Order the 25-foot inline connector extension cable assembly (CFG-0151-401) to extend the 100W-R with the
inline connector.
Caution Extension cable lengths must not exceed 300 ft. Extension cabling from Itron is stranded,
tinned, and pre-bonded for reliability and proper connection to gel cap connectors. Extension
cabling manufactured by non-approved Itron manufacturers may result in unreliable and
problematic connections. Contact Itron Support for more information.