Using Eagle Research Field Manager to Change the XARTU Corrector Settings
1. Open the Eagle Research Field Manager from the Start menu or the desktop shortcut.
2. Click Connect on the upper left corner of the Field Manager window.
3. Select the following parameters:
–
Connection Type: Direct
–
Communications Port: Enter your computer’s port number.
–
Baud Rate: Enter the baud rate for the XARTU-1 corrector.
4. Verify that the time and station name are correct.
5. Click View/Config.
Click OK.
6. Click the Setup Parameters tab at the bottom of the parameters window.
7. The Meter Setup and Accumulation Multipliers window opens. Set up the meter and
accumulation multipliers as appropriate for your installation.
Cellular 500G Module Remote Mount Installation Guide 4 Specific Meter Manufacturer Installation
October 11, 2021 815-0622-00 REV 000 Itron, Inc. Page 42 of 99