Installation Guide

Table Of Contents
Standard AdEM Romet 43-035-40 Cable Wiring
Connection Corrected count Uncorrected count
Romet cable wire Romet cable wire
Pulse Output 1+ Green White Red White
Blue Blue
Pulse Output 1- White Red Black Red
Note: This wiring configuration will not allow a cut cable tamper.
Romet PG9 Pigtail Cable Wiring
Connection Corrected count
Romet cable module
Pulse Output 1+ White White
Pulse Output 1- Red Red
Cut Cable Alarm Green Blue
Note: The pigtail cable is the cable extruding from the back of the AdEM corrector. You must select the pigtail
cable at the time the AdEM corrector is ordered.
Romet ECM2 Meter Wiring
The meter has three Form “A” outputs that can be configured at the factory to provide any
combination of the following three outputs:
Uncorrected volume (UNC VOL)
Corrected volume (COR VOL)
Alarm
The pulse weight for the volumetric outputs is configured in SetUp Mode at Menu items >
SET UNC OUT and Menu items > SET COR OUT. Since Setup Mode is fully configurable,
the ECM2 module is universally adaptable to all Romet TC meter bodies. Reference the
Romet technical manual for specific details on the ECM2.
Romet Cable Number 34-125-20
Cable pin Module wire
Corrected Uncorrected Alarm
A White and blue
B Red Red
C White and blue