We recommend Installation of this product by a Professional Contractor
Grab bars are to be installed in the critical support area as follows:
TUB - A horizontal grab bar(s) shall be installed on the back wall critical support area with a total minimum
length equal to 30% of the horizontal length of the critical support area. A horizontal or vertical grab bar(s)
shall be installed in the critical support area on either the service or non-service wall. A minimum horizontal
graspable length of 9" (229mm). A minimum vertical graspable length of 6" (152mm) and shall be installed in
the tub entrance area. See detail below.
SHOWER - A horizontal grab bar(s) shall be installed in the critical support area on either the service, back
or non-service wall. A minimum graspable length of 9" (229mm).
Recessed Tub/Shower Bathing Area
Critical support
area back wall
Critical support
area service wall
Critical support
24”
38” (Tub bathin
48” (Tub/Showe
6”
6”
6” Max.
RECESSED TUB/SHOWER BATHING AREA
CRITICAL SUPPORT
AREA BACK WALL
CRITICAL SUPPORT
AREA SERVICE WALL
38”
(60.96cm) (TUB BATHING)
48” (121.9cm) (TUB/SHOWER)
24”
(60.96cm)
CRITICAL SUPPORT AREA
NON-SERVICE WALL
6” MAX
(152mm)
6”
(152mm)
6”
(152mm)
GNG-660
11/19/09
We recommend Installation of this product by a Professional Contractor
Grab bars are to be installed in the critical support area as follows:
TUB - A horizontal grab bar(s) shall be installed on the back wall critical support area with a total minimum
length equal to 30% of the horizontal length of the critical support area. A horizontal or vertical grab bar(s)
shall be installed in the critical support area on either the service or non-service wall. A minimum horizontal
graspable length of 9" (229mm). A minimum vertical graspable length of 6" (152mm) and shall be installed in
the tub entrance area. See detail below.
SHOWER - A horizontal grab bar(s) shall be installed in the critical support area on either the service, back
or non-service wall. A minimum graspable length of 9" (229mm).
Recessed Tub/Shower Bathing Area
Critical support
area back wall
Critical support
area service wall
Critical support
24”
38” (Tub bathin
48” (Tub/Showe
6”
6”
6” Max.
RECESSED TUB/SHOWER BATHING AREA
CRITICAL SUPPORT
AREA BACK WALL
CRITICAL SUPPORT
AREA SERVICE WALL
38”
(60.96cm) (TUB BATHING)
48” (121.9cm) (TUB/SHOWER)
24”
(60.96cm)
CRITICAL SUPPORT AREA
NON-SERVICE WALL
6” MAX
(152mm)
6”
(152mm)
6”
(152mm)
GNG-660
11/19/09