Installation Guide

Salon™ Spa Bath
Installation and Operation www.jacuzzi.com Page 11
English
Electrical Connections
Risk of electric shock. Connect only to a circuit protected by a GFCI.
When using electrical products, basic precautions should always be followed:
Always follow local building and electrical codes.
Grounding is required. The unit should be installed and grounded by a qualied electrician.
Two separate GFCI protected circuits are required.
A separate, 240VAC, 20 Amp GFCI circuit is required for the heater and pump/motor.
A separate, 120VAC, 20 Amp GFCI circuit is required for the blower.
1
For the blower, install a 120 VAC, 15AMP, GFCI
duplex outlet to the stud wall underneath the
bathtub at 4˝ (101mm) above the oor. The duplex
outlet is not supplied.
Blower , Pump and Motor
The duplex outlet must be mounted 4˝ (101mm)
above the oor line, or in accordance with local
building and electrical codes.
T
M
(101mm)
Power Cord from Control
Box to GFCI Circuit
Heater
Risk of component overheat. Do not use electric extension cord to power this unit.
Operating the motor/pump without enough water in the bathtub can cause leaking and permanent damage.
At initial startup, the 8 button electronic control system enters an automatic self diagnostic program for 15-20
seconds. During the diagnostic program, the system will not accept user commands.
2
For the pump/motor and heater, install a 240
VAC, 20 AMP RATED GFCI outlet to the wall stud
underneath the bathtub, at least 4˝ (101mm) above
the oor. The outlet is not provided.
3
Power cords from the heater and the pump/motor
are routed to a fused junction box at the factory. A
supplied power cord from the junction box with a
240 VAC plug connects to the customer supplied
GFCI dedicated circuit.
4
With a #8 solid copper wire, ground the heater to
the house electrical panel or approved local bond. A
grounding lug is provided on the heater.
5
At initial start-up, and before each use thereafter
with power ON, push the GFCI test button. The
reset button should pop out.
Push the GFCI test button in to reset. If the interrupter fails to operate in this manner, there is a ground current
owing or a device malfunction, indicating the possibility of electrical shock.
Turn OFF power and do not use the bathtub until the source of the problem has been identied and corrected.
(101mm)
3-Prong Plug
Floor
120V Duplex Receptacle
(not supplied)
240V GFCI Protected Circuit