Installation Guide

106
General
Product
Information
Working
Safely
Tools for
Cutting and
Fastening
General
Installation
Requirements
General
Fastener
Requirements
Finishing and
Maintenance
HardieTrim®
Boards/Battens
HardieWrap®
Weather Barrier
HardieSoffit®
Panels
HardiePlank®
Lap Siding
HardieShingle®
Siding
HardiePanel®
Vertical Siding
ESR-1844 &
2290 Report
Appendix/
Glossary
The caulk joint method is
not recommended for the
ColorPlus
®
products
WARNING
!
VERTICAL JOINT TREATMENT
Treat vertical joints in HardiePanel
®
vertical siding by using one of the
following four methods:
1) Install the panels in
moderate contact.
2) Leave an appropriate gap
between panels (
1
/8 in. is the
most common), and caulk
using a high-quality paintable
caulk, that meets ASTM C-834
or C-920 requirements. (Not
recommended for ColorPlus)
Panels may be installed first with
caulk applied in the joints after
installation; or as an option, after
the first panel is installed, apply a
bead of caulk along the panel edge.
When the next panel is installed
against the first, the edge embeds
in the applied caulk creating a
thorough seal between the edges
of the panels.
3) Vertical joints may be covered
with wood or fiber-cement
batten strips. If James Hardie
®
siding or trim products are
ripped and used as batten
strips, paint or prime the cut
edges. Batten strips should
span the vertical joint by at least
3
/4 in. on each side.
4 Metal or PVC “H” moldings can
be used to join two sections of
HardiePanel siding.
TIP: Stainless steel fasteners are
recommended when installing
James Hardie products.
6d
screw
2
5
1 9
4d
common
1
.113 in. x .267 in. x 1.5 in.
ring shank
siding nail
5
.091 in. x .225 in. x 1.5 in.
roofing nail
9
No. 11ga 1.25 in. long
ET&F
13
[AKN100-0150NA]
.100 in. x .25 in. x 1.5 in.
2
.113 in. x .267 in. x 2 in.
6d
common
Fastening
Substrate
Fastening Types
Approved Fastener
1
2
9
wood
studs
24 in.
o.c.
16 in.
o.c.
7
13
steel
studs
16 in. o.c
or
24 in. o.c.
Ribbed Bugle-Head No. 8 (.323 in. x 1 in.)
screw
7
Installation of HardiePanel
®
Vertical Siding (continued)
3 Battened joint
4 H-Channel joint
1 Moderate contact joint
2 Caulked joint
Panels are butted together lightly.
1/8-in. gap left between
panels is lled with caulk.
(not applicable with ColorPlus)
HardieTrim
®
batten board covers
the joint between panels.
Note: The following outlines the recommended applications for ColorPlus and
Primed panels. Not all designs will be suitable for every application:
• Exposed fasteners or battens is the recommended application for ColorPlus products
• Do not use touch-up over fastener heads for smooth ColorPlus products - primed panel
recommended
• For ColorPlus panel applications that require fasteners in the eld, it is acceptable to
use touch-up over fasteners for Cedarmill and Stucco panel only, but correct touch-up
application is important. Some colors may show touch-up when applied over fasteners.
Trim is recommended to cover joints when appropriate.
A manufactured H-channel captures
the vertical edges of the panels.
12.3 12.4
12.612.5
HARDIEPANEL
SIDING FASTENER SPECIFICATIONS
The Fastener Specifications table shows fastener options for a variety of different nailing substrates. Please
refer to the applicable ESR report online (see back page) to determine which fastener meets your wind load