11. Configuration
11. 1 Measurement
The device has 4 measurement channels for voltage
measurement (V1 - V4 against Vref) and 4 measurement
channels for current measurement (I1 to I4).
Measured voltage and measured current
for the measurement channels 1-4 must
derive from the same network.
11. 1. 1 Baseline measurement
(measurement channels 1-3)
The baseline measurement uses measurement
channels 1-3. Use measurement channels 1-3
for measurement in three-phase systems.
You can choose one of 14 measurement
switches for the baseline measurement. The
relevant connection illustrations are provided
in section “6. 6 Connection variants”.
You can use parameter address “110” to set
the selected measurement switch.
Selectable measurement switches:
0 = 4w3m (factory default setting)
1 = 4w2m
2 = 4w2u
3 = 4w2i
4 = 3w3m
5 = 3w2m
6 = 3w2u
7 = 3w2i
8 = 2w2m
9 = 2w1m
10 = 4w3m_hv
11 = 4w2u_hv
12 = 3w2u_hv
13 = 3w2m_hv
Address Content
PRG
Fig. Display example; measurement switch for the baseline
measurement, address 110 with a content of 0.
11. 1. 2 Supporting measurement
(measurement channel 4)
The supporting measurement only uses
measurement channel 4.
Use measurement channel 4 when measuring
in single-phase systems or in three-phase
systems with symmetrical loads.
The frequency setting and the setting
for the relevant voltage are pulled automatically
from the baseline measurement settings.
You can choose one of 3 measurement
switches for the supporting measurement.
The relevant connection illustrations are
provided on page 23.
You can use parameter address “111” to set
the selected measurement switch.
Address Content
PRG
Selectable measurement switches:
0 = 2w1n (factory default setting)
1 = 3w1m
2 = 4w1m
Fig. Display example; measurement switch for the supporting
measurement, address 111 with a content of 0.