General
Tariff Conversion
The tariff conversion of the consumption meters is via the
addresses 618 and 624.
• Selectoneofthetariffs1to7bysettingordeletingbits
0 to 6.
• Bits7to15mustneverbesetandmustalwaysbe0.
• Tariff0isalwaysactiveandcanneverbeswitchedoff.
• Onlythebitsetwiththelowestvalueisevaluated.
000000 00000000
unused
tariff7(0=inactive;1=active)
tariff6(0=inactive;1=active)
tariff5(0=inactive;1=active)
tariff4(0=inactive;1=active)
tariff3(0=inactive;1=active)
tariff2(0=inactive;1=active)
tariff1(0=inactive;1=active)
0
00
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Bit:
Example:
Activate tariff 3 for „Effective energy“ and „Effective energy
drawn“.
• Setbit2toaddress618.
The meters for „Effective energy“ are active.
• Setbit2toaddress619.
The meters for „Effective energy drawn“ are active.
000010 00000000
unused
tariff7(0=inactive;1=active)
tariff6(0=inactive;1=active)
tariff5(0=inactive;1=active)
tariff4(0=inactive;1=active)
tariff3(0=inactive;1=active)
tariff2(0=inactive;1=active)
tariff1(0=inactive;1=active)
0
00
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Bit:
Example:
Setting tariff 3 and tariff 5 to one address at the
same time.
• Setbit2andbit4toaddress618.
Because only the bit set with the lowest value is evalua-
ted,onlytariff3isactive;bit4fortariff5isignored.
• Themetersfor„Effectiveenergy“(tariff3)areactive.
001010 00000000
unused
tariff7(0=inactive;1=active)
tariff6(0=inactive;1=active)
tariff5(0=inactive;1=active)
tariff4(0=inactive;1=active)
tariff3(0=inactive;1=active)
tariff2(0=inactive;1=active)
tariff1(0=inactive;1=active)
0
00
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Bit: