User manual
UMG 96RM
14
Modbus address list
Address Format RD/WR Unit Note Index
Parameter
These values can be set via the device buttons
0 SHORT RD/WR - Device adress 0..255
(*1)
1
1 SHORT RD/WR kbps Baudrate 0=9.6kbps 4
1=19.2kbps
2=38.4kbps
3=57.6kbps
4=115.2kbps
2 SHORT RD/WR - Modbus Master
(Master=1onlyforversionethernet) 0,1 0
3 SHORT RD/WR - Stopbits(0=1bit,1=2bits) 0,1 0
10 FLOAT RD/WR A Current transformer I1, primary 0..1000000
(*2)
5
12 FLOAT RD/WR A Current transformer I1, sec. 1..5 5
14 FLOAT RD/WR V Voltage transformer V1, primary 0..1000000
(*2)
400
16 FLOAT RD/WR V Voltage transformer V1, sec. 100, 400 400
18 FLOAT RD/WR A Current transformer I2, primary 0..1000000
(*2)
5
20 FLOAT RD/WR A Current transformer I2, sec. 1..5 5
22 FLOAT RD/WR V Voltage transformer V2, primary 1..1000000 400
24 FLOAT RD/WR V Voltage transformer V2, sec. 100, 400 400
26 FLOAT RD/WR A Current transformer I3, primary 1..1000000 5
28 FLOAT RD/WR A Current transformer I3, sec. 1..5 5
30 FLOAT RD/WR V Voltage transformer V3, primary 1..1000000 400
32 FLOAT RD/WR V Voltage transformer V3, sec. 100, 400 400
34 SHORT RD/WR Hz Frequency determination 0, 45..65 0
0=Auto,45..65=Hz
35 SHORT RD/WR - Display contrast 0 .. 9 5
0 (low), 9 (high)
36 SHORT RD/WR - Background lighting 0 .. 9 6
0 (dark), 9 (bright)
37 SHORT RD/WR - Indication profile 0 .. 3 0
0..2=Fixindicationproles
3=Freeselectableindicationprole
38 SHORT RD/WR - Indication rotation profile 0 .. 3 0
0..2=Fixindicationrotationproles
Indication rotation profile
3=Freeselectableindication
rotation profile
39 SHORT RD/WR Sec. Rotation time 0 .. 60 0
40 SHORT RD/WR - Averaging time, I 0 .. 8* 6
41 SHORT RD/WR - Averaging time, P 0 .. 8* 6
42 SHORT RD/WR - Averaging time, U 0 .. 8* 6
45 INT RD/WR mA Threshold, current measurement L1..L3 0..50 5
50 SHORT RD/WR - Password 0 .. 999 0 (no password)
100 SHORT RD/WR - Address of measurement value, 0 .. 32000
digital output 1
101 SHORT RD/WR - Address of measurement value, 0 .. 32000
digital output 2
102 FLOAT RD/WR - Pulse valence, out 1 -1000000 .. + 1000000
104 FLOAT RD/WR - Pulse valence, out 2 -1000000 .. + 1000000
106 SHORT RD/WR - Min. pulse duration, 1..1000
digital output 1/2
107 SHORT RD/WR - Results of the Comparator group 1 0, 1
combine A, B, C
1=and,0=or
108 FLOAT RD/WR - Comparator 1A, limit -1000000 .. + 100000
110 SHORT RD/WR - Comparator 1A, 0 .. 32000
Address of measurement value
* 0=5Sec.;1=10Sec.;2=15Sec.;3=30Sec.;4=1Min.;5=5Min.;6=8Min.;7=10Min.;8=15Min.
(*1)
The values of 0 and 248 to 255 are reserved and should not be used.
(*2)
The adjustable value of 0 for the primary power transformer results no useful work values and should not be used.
DefaultAdjustment Area