User manual

110
UMG 96RM-P/-CBM
Table 1 - Parameter list
0 SHORT RD/WR - Device address 0..255 (*1) 1
1 SHORT RD/WR kbps baud rate (0=9.6kbps, 1=19.2kbps, 0..7 4
2=38.4kbps, 3= 57.6kbps, (5..7 only for
4=115.2kbps) internal use)
2 SHORT RD/WR - Modbus Master 0, 1 0
0=Slave
3 SHORT RD/WR - Stopbits (0=1Bit, 1=2Bits) 0, 1 0
10 FLOAT RD/WR A Current transformer I1, primary 0..1000000
(*2)
5
12 FLOAT RD/WR A Current transformer I1, sec. 1..5 5
14 FLOAT RD/WR V Voltage transformer V1, prim. 0..1000000
(*2)
400
16 FLOAT RD/WR V Voltage transformer V1, sec. 100, 400 400
18 FLOAT RD/WR A Current transformer I2, primary 0..1000000
(*2)
5
20 FLOAT RD/WR A Current transformer I2, sec. 1..5 5
Address Format RD/WR Unit Note Adjustment Range Default
Parameter and Modbus address list
The following excerpt from the parameter list contains
settings that are necessary for proper operation of the
UMG 96RM-P/-CBM, such as current transformers and
device addresses. The values in the parameter list can
be written and read.
In the excerpt, the measured value list files the measured
and calculated measured values, output status data
and recorded values so that they can be read.
C
A complete overview of the parameters and
measured values as well as explanations
regarding the selected measured values
is filed in the document “Modbus Address
List” on the CD or Internet.
C
The addresses contained in the descrip-
tion can be adjusted directly on the device
in the range from 0 to 800. The address
range above 1000 can only be processed
via modbus!
(*1)
The values 0 and 248 to 255 are reserved and must not be used.
(*2)
The adjustable value 0 does not produce any sensible energy values and must not be used.