Installation Guide
CONNECT RANGE TO GAS SUPPLY 
• When all connections have been made, check 
that all range controls are in the ‘OFF’ position 
and open the main gas supply valve. 
• Leak testing of the appliance shall be conduct-
ed according to the manufacturer’s instructions. 
Use some soapy water (50% water and 50% 
liquid  detergent) or  a  leak  detector  at  all joints 
and connections to check for leaks in the 
system. Open the valve and check for leaks by 
placing the liquid solution onto all gas connec-
tions. Bubbles around connections indicate a 
gas leak. If a leak appears, close the shut-off 
valve, and adjust connections. Do not use a 
flame to check for gas leaks. 
• The appliance must be isolated from the build-
ing’s gas supply piping system by closing its 
individual manual shut-off valve during any 
pressure testing of the gas supply piping system 
at test pressure equal to or less than ½ psi 
(3.5kPa). 
Gas shut-off valve
IMPORTANT: The range must be connected to a regulated gas supply. The supply 
line must be equipped with an approved external gas shut-off valve located near the 
range in an accessible location. Do not block access to the shut-off valve. 
• All connections to the gas piping must be wrench-tightened. Do not overtighten or 
allow pipes to turn when tightening. 
• Any pipe connections must be made using a thread sealant approved for gas 
connections. Failure to correctly install these items could lead to a gas leak and 
subsequent explosion. 
• Install male ½” flare union adapter to ½” NPT internal thread elbow at inlet of regu-
lator. On models equipped with standard double burners, install the male pipe thread 
end of the ½” flare union adapter to the ½” NPT internal thread at inlet of pressure 
regulator. Use a wrench on the regulator fitting to avoid damage. 
• Install male ½” or ¾” flare union adapter to the NPT internal thread of the manual 
shut-off valve, taking care to secure the shut-off valve to keep it from turning. 
• The gas supply pressure for checking the regulator setting is 7” (Natural Gas) and 
11” (LP gas). Connect flexible gas line connector to the regulator on the range. Posi-
tion range to permit connection at the shut-off valve.
17