JINKOSOLAR PHOTOVOLTAIC MODULE USER MANUAL EDITION 06/2021 (UL61730)
CONTENTS 1 1.1 1.2 General Information Overview Warnings 1 1 1 2 2.1 2.2 2.2.1 2.2.2 2.2.3 2.3 2.3.1 2.3.2 2.3.2.1 2.3.2.2 2.3.2.
1. General Information 1.1 Overview In order to ensure the PV modules are installed correctly, please read the following installation instructions carefully before modules are installed and used. Please remember that these products generate electricity and certain safety measures need to be taken to avoid danger. Make sure the module array is designed in such a way as not to exceed the maximum system voltage of any system component such as connectors or inverters.
• The fire rating of this module is valid only when mounted in the manner specified in the mechanical mounting instructions. • The module is considered to be in compliance with UL 61730 only when the module is mounted in the manner specified by the mounting instructions below. • All installations must be performed in compliance with the National Electrical Code (NEC) and modules installed in Canada need to follow Canadian Electric Code (CEC).
where supplied with the module and evaluated through the requirements in UL 61730, may be used for grounding connections in accordance with the instructions provided with the module. • Under normal conditions, a module is likely to experience conditions that produce more current and/or voltage than reported at standard test conditions. The requirements of the National Electrical Code (NEC) in Article 690 shall be followed to address these increased outputs.
• Do not use modules in an environment with aliphatic, aromatic, phenols, ketones, halogenated substance or mineral oil, which may chemically corrode the junction box. • Do not contact junction box connectors with oily substances (e.g. lubricant, rust inhibitor, etc.). 2. Installation 2.1 Installation Safety • Always wear protective head gear, insulating gloves, and safety shoes (with rubber soles) and other protective measures during installation.
Connector model name (female) Allowable mating connector model name(male) PV-KBT4/6II-UR(female) PV-KST4/6II-UR(male) PV-KBT4/6I-UR(female) PV-KST4/6I-UR(male) PV-KBT4-EVO2/6II-UR(female) PV-KST4-EVO2/6II-UR(male) PV-KBT4-EVO2/6I-UR(female) PV-KST4-EVO2/6I-UR(male) QC4.10, followed by -a5, followed by b1, followed by c12 or c13, followed by d3, and followed by e2 QC4.10, followed by -a5, followed by b1, followed by c12 or c13, followed by d3, and followed by e2 QC4.
2.2 Installation Condition 2.2.1 Climate Condition Please install the modules in the following conditions: a) Operating temperature: –40°C (-40°F) to 85°C (185°F). b) Humidity: < 85RH%. c) Ambient air temperature range of -40°C to + 40°C. *Note: The mechanical load bearing (include wind and snow loads) of the module is based on the approved mounting methods. The professional system installer must be responsible for mechanical load calculation according to the system design. 2.2.
then the angle chosen should be adequate during the rest of the year. For grid-connected installations where the PV modules are attached to a permanent structure, PV modules should be tilted so that the energy production from the PV modules will be maximized on an annual basis. The System Fire Class Rating of a module or panel in a roof mounted system should meet local code requirements in order to achieve the specified System Fire Class Rating for a non-BIPV module or panel. A minimum slope of 22.
2.3.1 Mounting with Bolts The frame of each module has 8 mounting holes or 12 mounting holes used to secure the module to support structure. The module frame must be attached to a mounting rail using M8 corrosion-proof bolts together with spring washers and flat washers in eight symmetrical locations on the PV module. The applied torque value should be big enough to fix the modules steadily. The torque value for M8 bolt is 16~20 N*m and M6 bolt is 8 N*m.
2.3.2 Mounting with Clamps The module clamps should not come into contact with the front glass and must not deform the frame. Be sure to avoid shading effects from the module clamps. The module frame is not to be modified under any circumstances. When choosing this type of clampmounting method, please be sure to use at least four clamps on each module. Two clamps should be attached on each long side of the module. The applied torque value should be high enough to mount the modules steadily.
Clamp type Dimension (mm) End Clamp (40 mm thickness) 39 x 50 x 42 39 x 60 x 42 (For 1.5mm thickness frame) End Clamp (35 mm thickness) 41.5 x 50 x 40 Middle Clamp (40 mm & 35 mm thickness) Composition material 42 x 50 x 28 42 x 60 x 28 (For 1.5mm thickness frame) Q R P 13.5 15 2.5 Aluminum-alloy Table 3: Mechanical dimensions, specification and material when modules installed with mid Clamp 2.3.2.
Dimension (mm) Module type A*B*C J K 2031*1008*40 280 420 2031*1008*35 A/4-50 A/4+50 1704*1008*35*35 280 420 1704*1008*35 A/4-50 A/4+50 Group 5 & 19 & 21 2008*1002*40 280 420 Group 6 & 20 & 22 1684*1002*35 280 420 Group 7 & 14 & 23 & 26 2182*1029*40 2182*1032*40 430 570 Group 8 & 15 & 24 & 27 1855*1029*35 1855*1032*35 280 420 2205*1032*40 430 570 2205*1032*35 A/4-50 A/4+50 Group 11 1878*1032*35 280 420 Group 12 & 17 2167*998*40 380 520 Group 13 & 18 1840*998*3
Dimension (mm) Module type Max. Test Pressure: 5400Pa (positive) & 2400Pa (negative) mechanical load Note: A is the length of the long side of the module A*B*C Group 39 & 48 & 52 Group 53 1718*1134*35 1718*1134*40 2096*1039*40 J K A/4-50 A/4+50 A/4-50 A/4+50 Table 4: Mechanical dimensions when modules installed at long side with Clamp 2.3.2.2 Clamping Mounting on Short Sides of the Frames Figure 5: Installation of clamps on short side of frames Dimension (mm) Module type Max.
2.3.2.3 Clamping Mounting on Long/Short Sides Figure 6: Installation of clamps on long/short side of frame Dimension (mm) Max.
2. PV modules connected in series should have similar current, and modules must not be connected together to create a voltage higher than the permitted system voltage. The maximum number of modules in series depends on system design, the type of inverter used, and environmental conditions. 3. The maximum current rating of overcurrent protection in an array string can be found on the product label or in the product datasheet.
Figure 7: Ground Installation PV modules 7. Follow the requirements of applicable local and national electrical codes. 8. These modules contain factory installed bypass diodes. If these modules are incorrectly connected to each other, the bypass diodes, cable, or junction box may be damaged. 9. The module shall wire in accordance with the NEC. The grounding method of the frame of arrays shall comply with the NEC, article 250. 10. CNL model shall be in accordance with CSA C22.
13. Jinko Solar requires the negative grounding of the inverter when a system is installed with standard PV solar modules. Alternatively, a ‘charge-equalizing’ device may be used to mitigate the effects of the Potential Induced Degradation (PID) phenomenon that can occur in specific environments that the array is installed in. 4. Maintenance and Care 1. A building up of dust or dirt on the module’s front glass will result in a decreased energy output.
such information including product specification (without limitations) and suggestions do not constitute a warranty, expresses or implied. Jinko reserves the right to change the installation manual, the PV module, the electrical specifications, or product information sheets without prior notice.
Group 11 JKMxxxM-6RL3-TV (xxx =355~400, in increment of 5) Group 12 JKMxxxM-78H JKMxxxM-78H-Q JKMxxxM-78H-V JKMxxxM-78H-V-Q (xxx =405~465, in increment of 5) Group 13 JKMxxxM-66H JKMxxxM-66H-Q (xxx =340~390, in increment of 5) JKMxxxM-66H-V Group 14 JKMxxxN-7RL3-B (xxx =425~480, in increment of 5) Group 15 JKMxxxN-6RL3-B (xxx =360~405, in increment of 5) Group 16 JKMxxxN-6TL3-B (xxx =330~365, in increment of 5) Group 17 JKMxxxM-78HB (xxx =405~435, in increment of 5) Group 18 JKMxxxM-66
Group 24 JKMxxxM-6RL3-B JKMxxxM-6RL3-B-V (xxx =365~400, in increment of 5) Group 25 JKMxxxM-6TL3-B JKMxxxM-6TL3-B-V (xxx =335~365, in increment of 5) Group 26 JKMxxxN-7RL3 (xxx =430~475, in increment of 5) Group 27 JKMxxxN-6RL3 (xxx =365~400, in increment of 5) Group 28 JKMxxxN-6TL3 (xxx =335~365, in increment of 5) Group 29 JKMxxxM-78H-TV (xxx =405~450, in increment of 5) Group 30 JKMxxxM-66H-TV (xxx =345~380, in increment of 5) Group 31 JKMxxxM-7RL4-V JKMxxxM-7RL4 (xxx =535~590, in incre
Group 38 JKMxxxM-60HL4-V JKMxxxM-60HL4 (xxx =420~460, in increment of 5) JKMxxxM-54HL4-V Group 39 JKMxxxM-54HL4 (xxx =380~415, in increment of 5) Group 40 JKMxxxM-7RL4-TV (xxx =535~590, in increment of 5) Group 41 JKMxxxM-7TL4-TV (xxx =495~540, in increment of 5) Group 42 JKMxxxM-6RL4-TV (xxx =455~495, in increment of 5) Group 43 JKMxxxM-6TL4-TV (xxx =415~450, in increment of 5) Group 44 JKMxxxM-5RL4-TV (xxx =375~405, in increment of 5) Group 45 JKMxxxM-72HL4-TV (xxx =495~550, in incremen
Group 52 JKMxxxM-54HL4-B-V JKMxxxM-54HL4-B (xxx =380~400, in increment of 5) Group 53 JKMxxxM-72HLM-TV (xxx =425~455, in increment of 5) Notes: • V: Module with 1500V System Voltage • Blank: Module with 1000V System Voltage • H: Half-cut series module • L: G2 series module • TV: G3 bifacial module • RL3: G4 TR series module • B: Black backsheet series module • L4: Large cell of 182mm cell dimension • HLM: 166 large cell series module Appendix 2 : Electrical Specifications For the tolerance of electric
Module Type Group 2 xxx = 315 320 325 330 335 340 345 350 Maximum Power at STC (Pmax, Wp) 315 320 325 330 335 340 345 350 Maximum Power Voltage (Vmp, V) 32.7 32.9 33.1 33.24 33.40 33.62 33.76 33.94 Maximum Power Current (Imp, A) 9.63 9.73 9.82 9.93 10.03 10.11 10.22 10.31 Open-circuitVoltage (Voc, V) 39.9 40.1 40.3 40.39 40.46 40.60 40.75 40.87 Short-circuitCurrent (Isc, A) 9.99 10.07 10.15 10.25 10.34 10.43 10.53 10.
Module Type Group 4 xxx = 315 320 325 330 335 Maximum Power at STC (Pmax, Wp) 315 320 325 330 335 Maximum Power Voltage (Vmp, V) 33.00 33.17 33.38 33.51 33.68 Maximum Power Current (Imp, A) 9.55 9.65 9.74 9.85 9.95 Open-circuit Voltage (Voc, V) 40.19 40.32 40.43 40.56 40.73 Short-circuit Current (Isc, A) 10.12 10.23 10.32 10.43 10.53 Maximum system Voltage 1500VDC Dimensions 1704*1008*35mm (67.09*39.69*1.
Module Type Group 6 xxx = 330 335 340 345 350 Maximum Power at STC (Pmax, Wp) 330 335 340 345 350 Maximum Power Voltage (Vmp, V) 33.54 33.74 33.93 34.12 34.31 Maximum Power Current (Imp, A) 9.84 9.93 10.02 10.11 10.20 Open-circuit Voltage (Voc, V) 40.60 40.80 41.00 41.20 41.40 Short-circuit Current (Isc, A) 10.61 10.73 10.82 10.91 11.00 Maximum system Voltage 1500VDC/1000VDC Dimensions 1684*1002*35mm (66.30*39.45*1.
Module Type Group 8 xxx = 365 370 375 380 385 390 395 400 Maximum Power at STC (Pmax, Wp) 365 370 375 380 385 390 395 400 Maximum Power Voltage (Vmp, V) 36.00 36.10 36.20 36.30 36.39 36.49 36.58 36.67 Maximum Power Current (Imp, A) 10.14 10.25 10.36 10.47 10.58 10.69 10.80 10.91 Open-circuit Voltage (Voc, V) 43.32 43.41 43.49 43.58 43.66 43.75 43.93 44.12 Short-circuit Current (Isc, A) 10.94 11.03 11.12 11.21 11.30 11.39 11.48 11.
Module Type Group 11 xxx = 355 360 365 370 375 380 385 390 395 400 Maximum Power at STC (Pmax, Wp) 355 360 365 370 375 380 385 390 395 400 Maximum Power Voltage (Vmp, V) 36.49 36.55 36.61 36.67 36.73 36.79 36.85 36.90 36.95 37.01 Maximum Power Current (Imp, A) 9.73 9.85 9.97 10.09 10.21 10.33 10.45 10.57 10.69 10.81 Open-circuit Voltage (Voc, V) 43.32 43.41 43.49 43.58 43.66 43.75 43.83 43.92 44.00 44.05 Short-circuit Current (Isc, A) 10.45 10.55 10.
Module Type Group 13 xxx = 340 345 350 355 360 365 370 375 380 385 390 Maximum Power at STC (Pmax, Wp) 340 345 350 355 360 365 370 375 380 385 390 Maximum Power Voltage (Vmp, V) 36.56 36.67 36.77 36.87 36.97 37.06 37.15 37.24 37.33 37.42 37.54 Maximum Power Current (Imp, A) 9.30 9.74 9.85 9.96 10.07 10.18 10.29 10.39 Open-circuit Voltage (Voc, V) 43.24 43.32 43.41 43.49 43.58 43.66 43.75 44.02 44.09 44.17 44.29 Short-circuit Current (Isc, A) 10.20 10.27 10.34 10.
Module Type Group 15 xxx = 360 365 370 375 380 385 390 395 400 405 Maximum Power at STC (Pmax, Wp) 360 365 370 375 380 385 390 395 400 405 Maximum Power Voltage (Vmp, V) 36.51 36.72 36.93 37.13 37.33 37.53 37.72 37.91 38.10 38.28 Maximum Power Current (Imp, A) 9.86 10.02 10.10 10.18 10.26 10.34 10.42 10.50 10.58 Open-circuit Voltage (Voc, V) 44.12 44.33 44.54 44.74 44.94 45.14 45.33 45.52 45.71 45.89 Short-circuit Current (Isc, A) 10.44 10.52 10.60 10.68 10.76 10.
Module Type Group 17 xxx = 405 410 415 420 425 430 435 Maximum Power at STC (Pmax, Wp) 405 410 415 420 425 430 435 Maximum Power Voltage (Vmp, V) 43.23 43.3 43.37 43.44 43.51 43.57 43.64 Maximum Power Current (Imp, A) 9.37 9.47 9.57 9.77 9.87 9.97 Open-circuit Voltage (Voc, V) 51.55 51.58 51.61 51.64 51.67 51.7 51.73 Short-circuit Current (Isc, A) 10.01 10.11 10.21 10.31 10.41 10.51 10.61 Maximum system Voltage 1000VDC Dimensions 2167*998*40mm (85.31*39.29*1.
Module Type Group 19 xxx = 385 390 395 400 405 410 415 420 425 Maximum Power at STC (Pmax, Wp) 385 390 395 400 405 410 415 420 425 Maximum Power Voltage (Vmp, V) 39.65 39.76 39.86 39.96 40.06 40.16 40.26 40.35 40.44 Maximum Power Current (Imp, A) 9.71 10.01 10.11 10.21 10.31 10.41 10.51 Open-circuit Voltage (Voc, V) 47.90 48.05 48.20 48.35 48.50 48.65 48.80 48.95 49.10 Short-circuit Current (Isc, A) 10.42 10.48 10.54 10.60 10.66 10.72 10.78 10.84 10.90 9.81 9.
Module Type JINKOSOLAR.US Group 21 xxx = 380 385 390 395 400 Maximum Power at STC (Pmax, Wp) 380 385 390 395 400 Maximum Power Voltage (Vmp, V) 39.55 39.65 39.76 39.86 39.96 Maximum Power Current (Imp, A) 9.61 9.71 9.81 9.91 10.01 Open-circuit Voltage (Voc, V) 47.75 47.9 48.05 48.2 48.35 Short-circuit Current (Isc, A) 10.36 10.42 10.48 10.54 10.60 Maximum system Voltage 1000VDC Dimensions 2008*1002*40mm (79.06*39.45*1.
Module Type Group 23 xxx = 430 435 440 445 450 455 460 465 470 475 Maximum Power at STC (Pmax, Wp) 430 435 440 445 450 455 460 465 470 475 Maximum Power Voltage (Vmp, V) 43.18 43.29 43.40 43.50 43.61 43.72 43.81 43.91 44.01 44.11 Maximum Power Current (Imp, A) 9.96 10.05 10.14 10.23 10.32 10.41 10.50 10.59 10.68 10.77 Open-circuit Voltage (Voc, V) 51.77 51.87 51.97 52.07 52.17 52.48 52.81 53.14 53.47 53.80 Short-circuit Current (Isc, A) 10.78 10.87 10.96 11.
Module Type Group 25 xxx = 335 340 345 350 355 360 365 Maximum Power at STC (Pmax, Wp) 335 340 345 350 355 360 365 Maximum Power Voltage (Vmp, V) 33.30 33.40 33.50 33.66 33.81 33.97 34.12 Maximum Power Current (Imp, A) 10.06 10.18 10.30 10.40 10.50 10.60 10.70 Open-circuit Voltage (Voc, V) 39.90 40.00 40.10 40.26 40.41 40.57 40.72 Short-circuit Current (Isc, A) 10.77 10.89 11.01 11.11 11.21 11.31 11.
Module Type Group 27 xxx = 365 370 375 380 385 390 395 400 Maximum Power at STC (Pmax, Wp) 365 370 375 380 385 390 395 400 Maximum Power Voltage (Vmp, V) 35.79 35.86 35.92 35.99 36.05 36.11 36.18 36.24 Maximum Power Current (Imp, A) 10.20 10.32 10.44 10.56 10.68 10.80 10.92 11.04 Open-circuit Voltage (Voc, V) 43.95 44.14 44.32 44.51 44.69 44.88 45.07 45.25 Short-circuit Current (Isc, A) 11.03 11.13 11.23 11.33 11.43 11.53 11.63 11.
Module Type Group 29 xxx = 405 410 415 420 425 430 435 440 445 450 Maximum Power at STC (Pmax, Wp) 405 410 415 420 425 430 435 440 445 450 Maximum Power Voltage (Vmp, V) 42.90 43.03 43.20 43.35 43.50 43.66 43.85 43.92 43.98 44.04 Maximum Power Current (Imp, A) 9.44 9.77 9.85 9.92 10.02 10.12 10.22 Open-circuit Voltage (Voc, V) 51.55 51.58 51.61 51.64 51.67 51.70 51.80 51.90 52.00 52.10 Short-circuit Current (Isc, A) 10.15 10.20 10.28 10.36 10.44 10.52 10.60 10.
Module Type Group 31 xxx = 535 540 545 550 555 560 565 570 575 580 585 590 Maximum Power at STC (Pmax, Wp) 535 540 545 550 555 560 565 570 575 580 585 590 Maximum Power Voltage (Vmp, V) 43.46 43.59 43.71 43.83 43.95 44.06 44.18 44.29 44.40 44.52 44.63 44.73 Maximum Power Current (Imp, A) 12.31 12.39 12.47 12.55 12.63 12.71 12.79 12.87 12.95 13.03 13.11 13.19 Open-circuit Voltage (Voc, V) 53.04 53.14 53.24 53.34 53.44 53.54 53.64 53.74 53.84 53.94 54.04 54.
Module Type Group 33 xxx = 455 460 465 470 475 480 485 490 495 Maximum Power at STC (Pmax, Wp) 455 460 465 470 475 480 485 490 495 Maximum Power Voltage (Vmp, V) 36.73 36.80 36.88 36.95 37.03 37.10 37.17 37.24 37.31 Maximum Power Current (Imp, A) 12.39 12.50 12.61 12.72 12.83 12.94 13.05 13.16 13.27 Open-circuit Voltage (Voc, V) 44.66 44.74 44.82 44.90 44.98 45.06 45.14 45.22 45.30 Short-circuit Current (Isc, A) 13.29 13.36 13.43 13.50 13.57 13.64 13.71 13.78 13.
Module Type Group 35 xxx = 375 380 385 390 395 400 405 Maximum Power at STC (Pmax, Wp) 375 380 385 390 395 400 405 Maximum Power Voltage (Vmp, V) 29.88 30.00 30.11 30.21 30.32 30.42 30.52 Maximum Power Current (Imp, A) 12.55 12.67 12.79 12.91 13.03 13.15 13.27 Open-circuit Voltage (Voc, V) 36.58 36.66 36.74 36.82 36.90 36.98 37.06 Short-circuit Current (Isc, A) 13.43 13.50 13.57 13.64 13.71 13.78 13.85 Maximum system Voltage 1500VDC/1000VDC Dimensions 1686*1134*35mm (66.
Module Type Group 37 xxx = 460 465 470 475 480 485 490 495 500 505 Maximum Power at STC (Pmax, Wp) 460 465 470 475 480 485 490 495 500 505 Maximum Power Voltage (Vmp, V) 36.80 36.88 36.95 37.03 37.10 37.17 37.24 37.31 37.46 37.61 Maximum Power Current (Imp, A) 12.50 12.61 12.72 12.83 12.94 13.05 13.16 13.27 13.35 13.43 Open-circuit Voltage (Voc, V) 44.74 44.82 44.90 44.98 45.06 45.14 45.22 45.30 45.45 45.60 Short-circuit Current (Isc, A) 13.36 13.43 13.50 13.57 13.
Module Type Group 39 xxx = 380 385 390 395 400 405 410 415 Maximum Power at STC (Pmax, Wp) 380 385 390 395 400 405 410 415 Maximum Power Voltage (Vmp, V) 30.00 30.11 30.21 30.32 30.42 30.52 30.62 30.79 Maximum Power Current (Imp, A) 12.67 12.79 12.91 13.03 13.15 13.27 13.39 13.48 Open-circuit Voltage (Voc, V) 36.66 36.74 36.82 36.90 36.98 37.06 37.14 37.31 Short-circuit Current (Isc, A) 13.50 13.57 13.64 13.71 13.78 13.85 13.92 14.
Module Type Group 41 xxx = 495 500 505 510 515 520 525 530 535 540 Maximum Power at STC (Pmax, Wp) 495 500 505 510 515 520 525 530 535 540 Maximum Power Voltage (Vmp, V) 39.96 40.07 40.18 40.29 40.40 40.50 40.61 40.71 40.81 40.91 Maximum Power Current (Imp, A) 12.39 12.48 12.57 12.66 12.75 12.84 12.93 13.02 13.11 13.20 Open-circuit Voltage (Voc, V) 48.82 48.90 48.98 49.05 49.12 49.20 49.27 49.35 49.42 49.49 Short-circuit Current (Isc, A) 13.18 13.25 13.32 13.40 13.
Module Type Group 43 xxx = 415 420 425 430 435 440 445 450 Maximum Power at STC (Pmax, Wp) 415 420 425 430 435 440 445 450 Maximum Power Voltage (Vmp, V) 33.39 33.50 33.60 33.70 33.80 33.90 34.00 34.15 Maximum Power Current (Imp, A) 12.43 12.54 12.65 12.76 12.87 12.98 13.09 13.18 Open-circuit Voltage (Voc, V) 40.64 40.73 40.82 40.91 41.00 41.09 41.18 41.33 Short-circuit Current (Isc, A) 13.31 13.39 13.47 13.55 13.63 13.71 13.79 13.
Module Type Group 45 xxx = 495 500 505 510 515 520 525 530 535 540 545 550 Maximum Power at STC (Pmax, Wp) 495 500 505 510 515 520 525 530 535 540 545 550 Maximum Power Voltage (Vmp, V) 39.96 40.07 40.18 40.29 40.40 40.50 40.61 40.71 40.81 40.91 41.07 41.23 Maximum Power Current (Imp, A) 12.39 12.48 12.57 12.66 12.75 12.84 12.93 13.02 13.11 13.20 13.27 13.34 Open-circuit Voltage (Voc, V) 48.82 48.90 48.98 49.05 49.12 49.20 49.27 49.35 49.42 49.
Module Type Group 47 xxx = 415 420 425 430 435 440 445 450 455 Maximum Power at STC (Pmax, Wp) 415 420 425 430 435 440 445 450 455 Maximum Power Voltage (Vmp, V) 33.39 33.50 33.60 33.70 33.80 33.90 34.00 34.15 34.29 Maximum Power Current (Imp, A) 12.43 12.54 12.65 12.76 12.87 12.98 13.09 13.18 13.27 Open-circuit Voltage (Voc, V) 40.64 40.73 40.82 40.91 41.00 41.09 41.18 41.33 41.47 Short-circuit Current (Isc, A) 13.31 13.39 13.47 13.55 13.63 13.71 13.79 13.87 13.
Module Type JINKOSOLAR.US Group 49 xxx = 510 515 520 525 530 535 Maximum Power at STC (Pmax, Wp) 510 515 520 525 530 535 Maximum Power Voltage (Vmp, V) 41.23 41.40 41.57 41.74 41.90 42.06 Maximum Power Current (Imp, A) 12.37 12.44 12.51 12.58 12.65 12.72 Open-circuit Voltage (Voc, V) 49.00 49.17 49.34 49.51 49.67 49.83 Short-circuit Current (Isc, A) 13.21 13.28 13.35 13.42 13.49 13.56 Maximum system Voltage 1500VDC/1000VDC Dimensions 2274*1134*35mm (89.52*44.
Module Type JINKOSOLAR.US Group 51 xxx = 425 430 435 440 445 Maximum Power at STC (Pmax, Wp) 425 430 435 440 445 Maximum Power Voltage (Vmp, V) 34.06 34.24 34.42 34.59 34.77 Maximum Power Current (Imp, A) 12.48 12.56 12.64 12.72 12.80 Open-circuit Voltage (Voc, V) 40.83 41.01 41.19 41.36 41.54 Short-circuit Current (Isc, A) 13.24 13.32 13.40 13.48 13.56 Maximum system Voltage 1500VDC/1000VDC Dimensions 1903*1134*35mm (74.92*44.65*1.38 inch) 1903*1134*40mm (74.92*44.
Module Type JINKOSOLAR.US Group 53 xxx = 425 325 330 335 340 345 350 Maximum Power at STC (Pmax, Wp) 425 325 330 335 340 345 350 Maximum Power Voltage (Vmp, V) 40.40 33.13 33.24 33.37 33.47 33.60 33.72 Maximum Power Current (Imp, A) 10.52 9.81 9.93 10.04 10.16 10.27 10.38 Open-circuit Voltage (Voc, V) 48.56 40.08 40.21 40.34 40.47 40.60 40.73 Short-circuit Current (Isc, A) 11.21 10.46 10.52 10.58 10.64 10.70 10.
JINKOSOLAR.
Note JINKOSOLAR.