User Manual

9.57
L2906H, 2906H, 3507H, 619A, 723A, 29.6LP, 29.6, 35.7
Electrical System
PLA TFORM OPTION
NOT
CONFIGURED
2311 1 The UGM wi ll also disregard all
commands from the platform
station.
The UGM will use the platform
attached response curves.
If the PLATFORM ATTACHED
option has not been configured in
the MACHINE SETUP menu and a
platform attached state is detected
or the UGM detects a HI GH on J7-1
or J7-2.
Power cycle.
STABILIZERS NOT
CONFIGURED
2312 1 The UGM will ignore all stabilizer
function requests from t he joystick.
If the S1 button on the cabin’s
joystick is activated and the
STABILIZERS option has not been
configured in the MACHINE SETUP
menu and STABILIZERS are a
configurable for the sel ected
MODEL.
The S1
button on the
cabin joystick
is released.
FRAME LEVEL NOT
CONFIGURED
2313 1 The UGM wil l ignore all f rame level
function requests on UGM inputs
J4-17 and J4-9.
If J4-17 Frame Leveling Right or
J4-9 Frame Leveling Left inputs are
HIGH and the FRAME LEVEL
option has not been configured in
the MACHINE SETUP menu.
J4-17 or J4-9
goes LOW.
OPERATING
STATION
SELECTION
INVALID
2314 1 The directional symbol “N” will be
displayed in the operators cabin
display LCD.
The transmission will be
commanded to neutral and drive
will not be permitted.
Immediately deactivate and inhibit
all hydraulic function operation.
If UGM inputs J7-3 Ground Mode
and J7-2 Platform Mode both are
HIGH during operation.
Power cycle.
Message Fault
Code
Indicators Other Actions Taken Trigger for Fault Latch Until