User Manual

Electrical System
9.62
L2906H, 2906H, 3507H, 619A, 723A, 29.6LP, 29.6, 35.7
KEYPAD CANCEL
BUTTON – INVALID
SIGNAL
2340 1 Disregard all signal changes until
switch state transitions t o LOW.
The UGM detects the keypad
CANCEL button is HIGH at power
up or for a period of 7 seconds or
longer.
Power cyc led.
KEYPAD UP
BUTTON – INVALID
SIGNAL
2341 1 Disregard all signal changes until
switch state transitions t o LOW.
The UGM detects the keypad UP
button is HIGH at power up or for a
period of 7 seconds or longer.
Power cyc led.
KEYPAD DOWN
BUTTON – INVALID
SIGNAL
2342 1 Disregard all signal changes until
switch state transitions t o LOW.
The UGM detects the keypad
DOWN button is HIGH at power up
or for a period of 7 seconds or
longer.
Power cyc led.
BOOM ANGLE
SENSOR – NOT
CALIBRATED
2343 1 Assign a f ixed boom angle value of
99×, as other functions will then
fault to safe conditions.
Display the fixed boom angle value
of ‘99’ on the operator’s cabin
display.
Derate the MAX LIFT UP in the
PERSONALITIES menu screen by
the LIFT UP DERATE value in the
Constant Data tables.
Ignore all hydraulic function
requests from the platform module.
The UGM detects no calibration has
been completed.
A valid boom
angle sensor
calibration is
completed.
BOOM ANGLE
SENSOR – OUT OF
RANGE HIGH
2344 1 Display the fixed boom angle value
of ‘99’ on the operator’s cabin
display.
Temporarily assign a fixed boom
angle value of 99×.
If a calibration is in progress, fail
boom angle sensor calibration
(“CA LI BRATION: SENSOR
FAULT”).
Derate the MAX LIFT UP in the
PERSONALITIES menu screen by
the LIFT UP DERATE value in the
Constant Data tables.
Ignore all hydraulic function
requests from the platform module.
During operation or calibration, the
UGM detects a value at this input of
more than 4.4V.
Power cyc led.
BOOM ANGLE
SENSOR – OUT OF
RANGE LOW
2345 1 Display the fixed boom angle value
of ‘99’ on the operator’s cabin
display.
Temporarily assign a fixed boom
angle value of 99×.
If a calibration is in progress, fail
boom angle sensor calibration
(“CA LI BRATION: SENSOR
FAULT”).
Derate the MAX LIFT UP in the
PERSONALITIES menu screen by
the LIFT UP DERATE value in the
Constant Data tables.
²Ignore all hydraulic function
requests from the platform module.
During operation or calibration, the
UGM detects a value at this input of
less than 0.6V.
Power cyc led.
Message Fault
Code
Indicators Other Actions Taken Tri gge r for Fault Latch Until