User Manual

9.69
L2906H, 2906H, 3507H, 619A, 723A, 29.6LP, 29.6, 35.7
Electrical System
MAIN LIFT DOWN
VALVE
OPEN CIRCUIT
33184 1 Deactivate output J2-22 Main Lift
Down Valve.
The UGM detects an open circuit at
this output or the UGM detects a
CURRENT FEEDBACK LOST
condition and sets an internal flag t o
determine if this fault condition is
the reason for the fault.
Power cycled.
MAIN LIFT DOWN
VALVE
SHORT TO
GROUND
33185 1 Deactivate output J2-22 Main Lift
Down Valve.
Decouple/disable current feedback
input J3-2 Lift Return (Disabl es Lift
Up and Down).
The UGM detects a short to ground
at this output or the UGM detects a
CURRENT FEEDBACK LOST
condition and sets an internal flag t o
determine if this fault condition is
the reason for the fault.
Power cycled.
MAIN TELESCOPE
OUT VAL V E – OPEN
CIRCUIT
33186 1 Deactivate output J2-35 Main
Telescope Out Valve.
The UGM detects an open circuit at
this output or the UGM detects a
CURRENT FEEDBACK LOST
condition and sets an internal flag t o
determine if this fault condition is
the reason why.
Power cycled.
MAIN TELESCOPE
VALVESSHORT
TO BATTERY
33187 1 Deactivate output J2-35 Main
Telescope Out Valve.
Deactivate output J2-34 Main
Telescope In Valve.
Decouple/disable current feedback
input J3-4 Telescope Return
(Disables Telescope Out and In).
The UGM detects a short to battery
at this output.
Power cycled.
MAIN TELESCOPE
OUT V ALVE –
SHORT TO
GROUND
33188 1 Deactivate output J2-35 Main
Telescope Out Valve.
Decouple/disable current feedback
input J3-4 Telescope Return
(Disables Telescope Out and In).
The UGM detects a short to ground
at this output or the UGM detects a
CURRENT FEEDBACK LOST
condition and sets an internal flag t o
determine if this fault condition is
the reason for the fault.
Power cycled.
MAIN TELESCOPE
IN VALVE – OPEN
CIRCUIT
33189 1 Deactivate output J2-34 Main
Telescope In Valve.
The UGM detects an open circuit at
this output or the UGM detects a
CURRENT FEEDBACK LOST
condition and sets an internal flag t o
determine if this fault condition is
the reason for the fault.
Power cycled.
MAIN TELESCOPE
IN VALVE – SHORT
TO GROUND
33190 1 Deactivate output J2-34 Main
Telescope In Valve.
Decouple/disable current feedback
input J3-4 Telescope Return
(Disables Telescope Out and In).
The UGM detects a short to ground
at this output or the UGM detects a
CURRENT FEEDBACK LOST
condition and sets an internal flag t o
determine if this fault condition is
the reason for the fault.
Power cycled.
FORK TILT UP
VALVE
OPEN CIRCUIT
33191 1 Deactivate output J2-8 F ork T ilt Up
Valve.
The UGM detects an open circuit at
this output or the UGM detects a
CURRENT FEEDBACK LOST
condition and sets an internal flag t o
determine if this fault condition is
the reason for the fault.
Pow
er cycled.
Message Fault
Code
Indicators Other Actions Taken Trigger for Fault Latch Until