User Manual

Electrical System
9.70
L2906H, 2906H, 3507H, 619A, 723A, 29.6LP, 29.6, 35.7
FORK TILT VA LVES
– SHORT TO
BATTERY
33192 1 Deactivate output J2-8 Fork Tilt Up
Valve.
Deactivate output J2-19 Fork Tilt
Down Valve.
Decouple/disable current feedback
input J3-6 Tilt Return (Disables
Fork Tilt Up and Down).
The UGM detects a short to battery
at this output.
Power cyc led.
FORK TILT UP
VALVE – SHOR T T O
GROUND
33193 1 Deactivate output J2-8 Fork Tilt Up
Valve.
Decouple/disable current feedback
input J3-6 Tilt Return (Disables
Fork Tilt Up and Down).
The UGM detects a short to ground
at this output or the UGM detects a
CURRENT FEEDBACK LOST
condition and sets an internal flag to
determine if this fault condition is
the reason for the fault.
Power cyc led.
FORK TILT DOWN
VALVE
OPEN CIRCUIT
33194 1 Deactivate output J2-19 Fork Tilt
Down Valve.
The UGM detects an open circuit at
this output or the UGM detects a
CURRENT FEEDBACK LOST
condition and sets an internal flag to
determine if this fault condition is
the reason for the fault.
Power cyc led.
FORK TILT DOWN
VALVE – SHOR T T O
GROUND
33195 1 Deactivate output J2-19 Fork Tilt
Down Valve.
Decouple/disable current feedback
input J3-6 Tilt Return (Disables
Fork Tilt Up and Down).
The UGM detects a short to ground
at this output or the UGM detects a
CURRENT FEEDBACK LOST
condition and sets an internal flag to
determine if this fault condition is
the reason for the fault.
Power cyc led.
AUXILIAR Y FUNC-
TION-A VALVE
OPEN CIRCUIT
33196 1 Deactivate output J2-9 Auxiliary
Function-A Valve.
Deactivate and inhibit the
Continuous Auxiliary Hydraulics
feature.
T urn OFF the Continuous Auxiliary
Hydraulics indicator.
The UGM detects an open circuit at
this output or the UGM detects a
CURRENT FEEDBACK LOST
condition and sets an internal flag to
determine if this fault condition is
the reason for the fault.
Power cyc led.
AUXILIARY
FUNCTIO-A/B
VALVES – SHORT
TO BATTERY
33197 1 Deactivate output J2-9 Auxiliary
Function-A Valve.
Decouple/disable current feedback
input J3-14 Aux Return (Disables
Auxiliary Function-A and
Function-B) .
Deactivate and inhibit the
Continuous Auxiliary Hydraulics
feature.
T urn OFF the Continuous Auxiliary
Hydraulics indicator.
The UGM detects a short to battery
at this output.
Power cyc led.
Message Fault
Code
Indicators Other Actions Taken Tri gge r for Fault Latch Until