User Manual

9.71
L2906H, 2906H, 3507H, 619A, 723A, 29.6LP, 29.6, 35.7
Electrical System
AUXILIARY
FUNCTION-A
VALVE– SHO RT TO
GROUND
33198 1 Deactivate output J2-9 Auxiliary
Function-A Valve.
Decouple/disable current feedback
input J3-14 Aux Return (Disables
Auxiliary Function-A and
Function-B).
Deactivate and inhibit the
Continuous Auxiliary Hydraulics
feature.
Turn OFF the Continuous Auxiliary
Hydraulics indicator.
The UGM detects a short to ground
at this output or the UGM detects a
CURRENT FEEDBACK LOST
condition and sets an internal flag t o
determine if this fault condition is
the reason for the fault.
Power cycled.
AUXILIARY
FUNCTION-B V AL VE
– OPEN CIRCUIT
33199 1 Deactivate output J2-20 Auxiliary
Function-B Valve.
Deactivate and inhibit the
Continuous Auxiliary Hydraulics
feature.
Turn OFF the Continuous Auxiliary
Hydraulics indicator.
The UGM detects an open circuit at
this output or the UGM detects a
CURRENT FEEDBACK LOST
condition and sets an internal flag t o
determine if this fault condition is
the reason for the fault.
Power cycled.
AUXILIARY
FUNCTION-B V AL VE
– SHORT TO
GROUND
33200 1 Deactivate output J2-20 Auxiliary
Function-B Valve.
Decouple/disable current feedback
input J3-14 Aux Return (Disables
Auxiliary Function-A and
Function-B).
Deactivate and inhibit the
Continuous Auxiliary Hydraulics
feature.
Turn OFF the Continuous Auxiliary
Hydraulics indicator.
The UGM detects a short to ground
at this output or the UGM detects a
CURRENT FEEDBACK LOST
condition and sets an internal flag t o
determine if this fault condition is
the reason for the fault.
Power cycled.
STABILIZER/FRAME
LEVEL SP EED
VALVE
OPEN CIRCUIT
33201 1 Deactivate output J1-3 Stabilizer
and Frame Level Speed Valve .
The UGM is not configured for a
3508, 3509, 4008, or 4009 and the
UGM detects an open circuit at thi s
output or the UGM detects a
CURRENT FEEDBACK LOST
condition and sets an internal flag t o
determine if this fault condition is
the reason for the fault.
Power cycled.
STABILIZER/FRAME
LEVEL SP EED
VALVE – SHORT TO
BATTERY
33202 1 Deactivate output J1-3 Stabilizer
and Frame Level Speed Valve .
Decouple/disable current feedback
input J3-5 Stabilizer – Frame Level
Return (Disables Stabilizers and
Frame Leveling functions).
The UGM is not configured for a
3508, 3509, 4008, or 4009 and the
UGM detects a short to battery at
this output.
Power cycled.
STABILIZER/FRAME
LEVEL SP EED
VALVE – SHORT TO
GROUND
33203 1 Deactivate output J1-3 Stabilizer
and Frame Level Speed Valve .
Decouple/disable current feedback
input J3-5 Stabilizer – Frame Level
Return (Disables Stabilizers and
Frame Leveling functions).
The UGM is not configured for a
3508, 3509, 4008, or 4009 and the
UGM detects a short to ground at
this output or the UGM detects a
CURRENT FEEDBACK LOST
condition and sets an internal flag t o
det
ermine if this fault condition is
the reason for the fault.
Power cycled.
Message Fault
Code
Indicators Other Actions Taken Trigger for Fault Latch Until