SECTION 2 - PROCEDURES
3120884 – JLG Lift – 2-57
2/5
Flash code 2/5 indicates that a function is prevented due to a cutout.
BOOM PREVENTED - DRIVE SELECTED
A boom function is selected while a drive function is selected and drive cutout is configured to prevent
simultaneous drive & boom operation.
BOOM PREVENTED - FUNCTION CUTOUT ACTIVE
A boom function is selected while function cutout is active and configured to cutout boom functions.
DRI VE & BOO M P REVENTED - FUN CTION CUTOUT ACTIVE
Drive or a boom function is selected while function cutout is active and configured to cutout all functions.
DRIVE PREVENTED - ABOVE ELEVATION
Drive is selected while above elevation and drive cutout is configured to prevent drive.
DRIVE PREVENTED - BOOM MOVEMENT SELECTED
Drive is selected while a boom function is selected and drive cutout is configured to prevent simultaneous
drive & boom operation.
DRIVE PREVENTED - CHARGER CONNECTED
Drive is selected while the charger is on (indicated by drive cutout being active) and drive cutout is config-
ured to prevent drive.
DRIVE PREVENTED - TILT ED AND ABOVE ELEVATION
Drive is selected while drive cutout is active and drive cutout is configured to prevent drive.
TILT MODULE FAILURE: NOT COMMUNICATING
There is a p roblem with the positrac/tilt module; the con troller defaults to massively tilted a nd does not try to
prevent vehicle roll on the grade.
3/1
Flash code 3/1 indicates that a contactor did not close when energized.
LINE & DIRECTION CONTAC TORS MISWIRED
When the li ne contactor was closed tract ion point A went high (and the capacito r bank charge did not
increase to battery supply) - this occurs if the line contactor coil wiring is swapped with that for a direction
cont actor coil.
OPEN-CIRCUIT FORWARD DIRECT IO N CONTACTOR OR TRACTION MOTOR
Traction point A did not go hi gh when forward contactor was energized (this could be due to traction motor
open-circuit or a power wiring error).
OPEN-CIRCUIT LINE CONTACTOR OR TRACTION MOTOR
The capacitor bank charge did not increase to battery supply when line contactor was energized (this could
be due to a power wiring error).
OPEN-CIRCUIT REVERSE DIRECTION CONTACTOR
Traction point A did not go high when reverse contactor was energized (this could be due to traction motor
open-circuit or a power wiring error).
3/2
Flash code 3/2 indicates that a contactor did not open when energized.
WELDED LINE CONTACTOR
The ca pacitor bank charge did not decrease from battery supply when line contactor was deenergized (this
could be due to a power wiring error).
WARNING: If the line contactor is welded, the controller will not switch off when EMS or keyswitch is turned
off.
Table 2-8. Help Descripti ons and Fault Flash Codes