SECTION 2 - PROCEDURES
3120884 – JLG Lift – 2-59
6/6
Flash code 6/6 indicates problems with the CANbus.
48V PROTECTION TRIPPED - CHECK INTER-MODULE WIRING
The power module is not receiving acknowledgments from the platform or ground modules to transmitted
data, a nd the prot ec t ion circui t whi ch supplie s the platform and grou nd module s has tr ipped. This is proba-
bly due to wiring problems at the platform or ground module.
CANbus FAILURE: GROUND MODULE
The power module is receivin g from the plat form module but not the groun d module. This shou ld not be
possible!
CANbus FAILURE: PLATFORM MODULE
The power module is receiving from the ground module but not the platform module. This is probably due
to wiring problems between the platform and ground modules.
CANbus FAILURE: POWER MODULE The power module is not receiving acknowledgments from the plat-
form or ground modules to transmitted data. This is probably due to wiring problems between the ground
and powe r modules .
7/7
Flash code 7/7 indicates problems with a motor.
CAPACITOR BANK FAULT - CHECK POWER CIRCUITS
The capacitor bank is not charging. This is probably due to a power wiring error causing illegal current
drain; it could also be due to a very low battery supply.
OPEN-CIRCUI T PUMP MOTOR
Pump point A is collapsing when the pump MOSFETs are pulsed. Th is is probably due to an open circuit
pump motor or a power wiring error.
OPEN-CIRCUIT DIRECTIONAL CONTACTOR OR TRACTION MOTOR
Traction point A is collapsing when the traction MOSFETs are pulsed. This is probably due to an open cir-
cuit tr action mot or or a power wiri ng err or. NOTE: T his faul t is unl ikely t o be see n due to int eraction with
speed control...
PUMP POINT A LOW - CH EC K POW E R CI RC UIT S
Pump point A is near 0V when the pump MOSFETs are off. This is probably due to a power
STALLED TRACTION MOTOR
The power module traction MOSFET pro tection circuit is active. This is due to massive current drain and
could be a stalled traction motor or a power wiring error.
STALLED PUMP MOTOR
The power module pump MOSFET protection circuit is active. This is due to massive current drain and
could be a stalled pump motor or a power wiring error.
TRACTION MOTOR OVERLO A DED
The traction motor has been ope rating in current limit at a low percentage on for a period of time greater
than 10 seconds.
PUMP MOTOR OVERL OA DED
The pum p mo tor has been operating in current li mit at a lo w percentage on for a period of tim e greater than
10 seconds.
TRACTION CURRENT AT ZERO - CHECK SHUNT WIRING
Traction current measurement is at zero. This is probably due to an open-circuit between the current mea-
surement shunt and the power module.
TRACTION POINT A HIGH - CHECK POWER CI RC UI TS
Traction point A is near battery supply when neither direction contactor is energized and the traction MOS-
FETs are off. This could be due to a welded direction contactor or a power wiring error.
TRACTION POINT A L OW - CH ECK POWER CIRCUIT S
Traction point A is near 0V when neither direction contactor is energized and the traction MOSFETs are off.
This could be due to a power wiring error.
Table 2-8. Help Descripti ons and Fault Flash Codes