TROUBLESHOOTING GUIDELINES
TROUBLE SHOOTING
Pleasecheckguidelinesbelow.Foryoursafety,waterheaterserviceshouldbeperformedonlybyaqualiedservicetechnician.
ReadtheGENERALSAFETYINFORMATIONsectionrst.
INTELLI-VENT TROUBLESHOOTING CHART - RESIDENTIAL CONTROL
PROBLEM
SOLUTION
Inadequateornoearthground 1.Ensurethewalloutletisproperlygrounded.
1 sensedbytheIntelli-Vent™
control. 2.Ensureallgroundconnections/wiresonthe
waterheateraresecure.
PowersupplytoIntelli-Vent™ 1.Ensurethewalloutletisproperlywired.
2 controlhasreversedpolarityora
highresistancetoearthground. 2.Ensureallinternal120VACwiringconnectionsand
wiringharnesshavenoreversedwires.120VAC
“hot”wiremustconnecttotheon/offswitch.
3.Ensurethewalloutletisproperlygrounded.
4.Ensureallgroundconnections/wiresonthewater
heateraresecure.
Pressureswitchcircuitremaining 1.Ensureairpressureswitchcircuitwiringiscorrect
3 closedformorethan5seconds andtheairpressureswitchisnotjumpered.
afterheatingcyclebegins.
Blower does not start. 2.Securepowertowaterheater,checkcontinuityofair
pressureswitchcontactswithwiresdisconnected.
Service Note:
Disconnectpower-disconnectone A Ifpressureswitchcontactsshowcontinuity(closed
wirefromtheairpressureswitch circuit)replacethepressureswitch.
ortheventtemperaturelimit
switch.Turnpowerbackon- B Ifpressureswitchcontactsareopenandallwiring
blowershouldstart. iscorrect-turnthepowerofffor10-20seconds
thenonagaintocleartheerrorcode-iftheerror
codepersistsreplacetheIntelli-Vent™control.
Pressureswitchcircuitremainsopen 1.Ensuretheblowerisrunning-checkfor120VACto
4 longerthan5secondsaftertheblower theblowerwhentheheatingcyclebegins,checkthe
isenergized. wiring.Ifthecontroldoesnotenergizetheblower-
replacetheIntelli-Vent™control.Iftheblowerfailsto
Blower may run continuously in startwhenenergized-replacetheblowerassembly.
this condition.
2.Ensuretheairpressureswitchsensingtubeisproperly
connected-notkinkedordamaged.
3.Checkcontinuityofventtemperaturelimitswitch-replace
switchifcontactsremainopenunder160ºF(71°C).
4.Ensurethecorrectsizeofventpipe(2”,3”,4”)wasused
perinstallationmanualforventlength.Ensuremaximum
numberofelbowsorequivalentfeetofventpipehasnot
exceededmaximumlimits.
5.Ensuretherearenoobstructionsintheventpipe.
6.Checkairpressureswitchperformance-checkpressure
withadigitalmanometer-checkcontinuityofcontacts.
(seeservicenoteinleftcolumn)Iftheswitchproves
defective-replacetheairpressureswitchandorthe
blowerassemblyasrequired.
7.Ifairpressureswitchperformancetestresultsprove
theairpressureswitchisworkingproperlyanderror
code4persists-replacetheIntelli-Vent™control.
TheIntelli-Vent™controlhasdetected 1.Checkwiringtothehotsurfaceignitor-replaceignitor
5 anopenignitorcircuit. assemblyifwiringisdamagedorworn.
Service Note: 2.Checkignitorassemblyplugandthesocketonthe
Theresistance(ohms)ofahotsurface Intelli-Vent™bodyforgoodconnection.Replace
ignitorwillincreaseovertime.Ifthe ignitorassemblyand/orcontrolifnecessary.
resistanceatroomtemperatureisnear
18.8ohms-considerreplacingtheignitor 3.Checkresistanceofignitoratroomtemperature77ºF
asapreventativemeasure. (25°C)attheplugend.Replaceignitorifresistance
isnotwithin11.5and18.8ohmsatroomtemperature.
4.Ifresultsfromtheabovetestsweregoodanderror
code5persists-replacetheIntelli-Vent™control.
A B C
A B C
A B C
A B C
A B C