Brochure

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2013 Johnson Controls, Inc.
www.johnsoncontrols.com
1
CSD Series Current Devices
Code No. LIT-1900454
Issued April 5, 2013
Description
The Current Switch Device (CSD) Series of
digital output current switches are
non-intrusive devices designed to detect
current flowing through a cable or wire. A
cost-effective solution for monitoring on and
off status or proof of operation, these units are
ideal for monitoring very small current loads
on motors driving fans and blowers, pumps,
heating coils, and lighting.
The CSD models with command relays not
only monitor the current flowing through the
cable but also facilitate the start and stopping
of the motor.
These units also provide a universal
solid-state output and do not require a power
supply. Completely self-powered, these units
draw their power from current induced from
the cable or line being monitored.
CSD Series Current Devices are available in
the following types:
solid core, setpoint fixed
solid core, setpoint adjustable
solid core with command relay,
setpoint adjustable
split core, setpoint fixed
split core, setpoint adjustable
split core with command relay,
setpoint fixed
split core with command relay,
setpoint adjustable
12 VAC/VDC and 24 VAC/VDC accessory
command relays
Refer to the CSD Series Current Devices
Product Bulletin (LIT-12011292) for important
product application information.
Features
dual function — monitors current and motor
start and stop
100% solid-state output — has no moving
parts to fail
polarity insensitive output — provides
easier wiring
snap-in mounting bracket — simplifies
installation
small size — fits in tight enclosures
Fixed Setpoint Models
CSD-SF0C0-1 (solid core)
Setpoint fixed at 0.25 A
Current range — 0.25 to 200 A
CSD-CF0A0-1 (split core)
Setpoint fixed at 0.15 A
Current range — 0.15 to 200 A
CSD-CF0J0-1 (split core)
Setpoint fixed at 1.5 A
Current range — 1.5 to 200 A
CSD-CF0J1-1 (split core with 24 V command
relay)
Relay Single Pole, Single Throw (SPST),
Normally Open (N.O.), 10 A at 260 VAC,
5 A at 30 VDC
Actuation coil — 20–30 VAC/DC,
40–85 mA maximum
Setpoint fixed at 1.5 A
Current range — 1.5 to 200 A
Adjustable Setpoint Models
CSD-SA1E0-1 (solid core)
Multi-turn potentiometer — adjust setpoint
for application
Adjustable setpoint — wide range from
1.0 to 135 A
Two status Light-Emitting Diodes (LEDs)
— provide visual indication of off and on
status
CSD-SA1E1-1 (solid core with 24 V command
relay)
Multi-turn potentiometer — adjust setpoint
for application
Adjustable setpoint — wide range from
1.00 to 135 A
Relay SPST, N.O., 10 A at 260 VAC,
5 A at 30 VDC
Actuation coil — 20–30 VAC/DC,
40–85 mA maximum
Two Status LEDs — provide visual
indication of off and on status
CSD-CA1G0-1 (split core)
Multi-turn potentiometers — adjust setpoint
for application
Two status LEDs — provide visual
indication of off and on status
Adjustable setpoint — wide range from 1.25
to 135 A
CSD-CA1G1-1 (split core with 24 V command
relay)
Multi-turn potentiometers — adjust setpoint
for application
Adjustable setpoint — wide range from
1.25 to 135 A
Relay SPST, N.O., 10 A at 260 VAC,
5 A at 30 VDC
Actuation coil — 20–30 VAC/VDC,
40–85 mA maximum
Two status LEDs — provide visual
indication of off and on status
CSD-SA1E2-1 (solid core with 12 V command
relay
Multi-turn potentiometers — adjust setpoint
for application
Adjustable setpoint — wide range from
1.00 to 135 A
Relay SPST, N.O., 10 A at 260 VAC,
5 A at 30 VDC
Actuation coil — 10–14 VAC/VDC,
25–45 mA maximum
Two status LEDs — provide visual
indication of off and on status
Repair Information
If the CSD Series Current Device fails to
operate within its specifications, replace the
unit. For a replacement CSD Series Current
Device, contact the nearest
Johnson Controls® representative.
CSD Series Current Device

Summary of content (3 pages)