Product Overview
Table Of Contents
Technical specifications
Table 1: HL-69158NP Multi-function Humidity Device with Temperature Sensor technical specifications
Specification Description
Power requirements
Proportional output: 20 VAC to 30 VAC, 1.1 VA at 50/60 Hz or 14 VDC to 30 VDC at 22
mA
Relay output: 20 VAC to 30 VAC, 1.1 VA at 50/60 Hz or 20 VDC to 30 VDC at 22 mA
Wire gauge 16 AWG to 24 AWG; 18 AWG optimal
Humidity
Element: Capacitive
Setpoint: Adjustable from 60% RH to 95% RH
Proportional band: Adjustable from 5% RH to 30% RH
Temperature sensor
Type: Thin-film nickel
Resistance: 1K ohm at 70°F (21°C)
Accuracy: ±0.34°F (0.18°C) at 70°F (21°C)
Coefficient: Approximately +3 ohm/°F; 5 ohm/°C
Controller signal Input and output: 0 VDC to 10 VDC or 0 mA to 20 mA
Input impedance Voltage: 20K ohm Current: 500 ohm
Output load Voltage: ≥1K ohm Current: ≤500 ohm
Relay contact
Single-Pole, Single-Throw (SPST), normally open — open at setpoint and closed at
setpoint minus proportional band, stand-alone operation only
Relay contact rating
Maximum: 4A, 24 VAC, Class 2; Pilot Duty, 42.4 VA at 24 VAC
Minimum: 100 mA at 5 VDC
Ambient operating conditions
32°F to 150°F (0°C to 66°C); 0% RH to 100% RH noncondensing; 90°F (32°C)
maximum dew point
Ambient storage conditions -40°F to 150°F (-40°C to 66°C); 0% RH to 100% RH; 90°F (32°C) maximum dew point
Materials Blue plastic cover with blue housing and probe
Dimensions (H x W x D)
3.28 in. x 3.25 in. x 8.27 in. (83 mm x 83 mm x 210 mm)
Probe (L x D): 6.25 in. x 0.98 in. (159 mm x 25 mm)
Shipping weight 0.7 lb (0.03 kg)
Duct probe material 94-5V flammability rated per UL 94
Compliance
United States: UL Listed, CCN XAPX, File E27734; to UL 60730-1; and IEC 60730-2-13.
Plenum Rated (UL 2043)
Canada: cUL Listed, CCN XAPX7, File E27734; to CAN/CSA E60730-1; and CAN/
CSAE60730-2-13
Europe: CE Mark - Johnson Controls declares that this product is in compliance
with the essential requirements and other relevant provisions of the EMC Directive.
Australia and New Zealand: RCM Mark, Australia/NZ Emissions Compliant
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions
beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for
damages resulting from misapplication or misuse of its products.
HL-69158NP Multi-Function Humidity Device with Temperature Sensor Product Bulletin 5