user manual

898841-UIM-B-0113
Johnson Controls Unitary Products 15
REFRIGERANT PIPING CONNECTIONS
A Service port cap protects the service port core from contamination
and serves as the primary leak seal. To access service port:.
1. Remove service port cap with an appropriate sized wrench.
2. Connect gauge set to service port.
3. When testing is complete, replace service port cap and tighten as
follows:
a. With torque wrench - Finger tighten then torque cap per Table 11
requirements.
b. Without torque wrench - Finger tighten then use appropriate
sized wrench to turn an additional 1/6 turn clockwise.
Stem cap protects the valve stem from damage and serves as the pri-
mary seal. Replace the stem cap and tighten as follow:
1. With torque wrench - Finger tighten and use torque cap per Table
11.
2. Without torque wrench - Finger tighten then use an appropriate
sized wrench to turn an additional 1/12 turn clockwise.
INDOOR UNIT CONNECTION
Connect both liquid and gas pipes to indoor unit.
Apply a sealing cap or water-proof tape to prevent dust or water
from getting into the refrigerant piping before it is connected.
Apply a thin coat of refrigerant oil on the seal surface of the pipe.
For connection, first align the union tube and flared refrigerant
line with each other then tighten the flare nuts lightly at first to
obtain a smooth match.
Use tightening toque Table 11 as a guideline for indoor unit side
union joint section and tighten using two wrenches. Excessive
tightening may damage the flare section.
OUTDOOR UNIT CONNECTION
Apply a sealing cap or water proof tape to prevent dust or water
from getting into the refrigerant piping before it is connected.
Apply refrigerant lubricant to the matching surfaces of the flared
line set and union before connecting them together. This will
reduce refrigerant leaks.
Align the flared refrigerant line with valve connection then tighten
the flare nut lightly at first to obtain a smooth match. Use tighten-
ing toque Table 11 as a guideline.
FIGURE 32: Outdoor Unit Wiring Terminal Designations
OUTDOOR UNIT
TERMINALS
N(1)
23
L1 N
(DATA)
(NEUTRAL)
(GND)
N(1)
2
3
(NEUTRAL)
(GND)
(L1)
N(1)
23
L1 L2
(DATA)
(L2)
(GND)
N(1)
2
3
(GND)
(L1)
N(1) 2 3
N(1)
2
3
L1
L2
(L2)
(GND)
(L1)
(GND)
208-230V SYSTEMS
30 & 36 KBTU (208-230V)
SYSTEM ONLY
115V SYSTEMS
INDOOR UNIT TERMINALS
INDOOR UNIT TERMINALS
INDOOR UNIT TERMINALS
OUTDOOR UNIT
TERMINALS
OUTDOOR UNIT
TERMINALS
OUTDOOR UNIT
TERMINALS
(NEUTRAL)
(NEUTRAL)
(DATA)
Fasten flare nut with a torque wrench as specified in Table 9.
When fastened too tight, flare nut may break after a long period
and cause refrigerant to leak.
NOTICE
FIGURE 33: Indoor/Outdoor Piping Connections
FIGURE 34: Outdoor Line Set Connections
MALE FLARE
CONNECTION
APPLY REFRIGERANT
LUBRICANT HERE
A
B
OUTDOOR UNIT
LIQUID SIDE PIPING
(SMALLER DIAMETER)
TORQUE WRENCH
GAS SIDE PIPING
(BIGGER DIAMETER)