User Guide
Table Of Contents
M9000-560 Ball Valve Linkage Kit and M9000-561 Thermal Barrier Installation Instructions12
Mounting the Thermal Barrier
Figure 28 shows the optional M9000-561 Thermal
Barrier.
To mount the optional thermal barrier:
1. Install the thermal barrier drive shaft into the
thermal barrier by aligning the tab on the drive
shaft with the slot on the thermal barrier
(Figure 29).
2. Rotate the drive shaft to align marks on the top of
the thermal drive shaft with matching marks on the
valve stem.
3. Mount the thermal barrier onto the valve using the
four included M5x16 mm machine screws and four
M5 flange nuts. Tighten the screws to a
recommended torque of 21 to 25 lb·in
(2.4 to 2.8 N·m) (Figure 30).
4. Proceed to actuator mounting instructions. Follow
the same steps as mounting directly to the valve
when mounting the actuator to the thermal barrier.
Repair Information
If the M9000-560 Ball Valve Linkage Kit or M9000-561
Thermal Barrier fail to operate within the specifications,
replace the unit. For a replacement kit, contact the
nearest Johnson Controls® representative.
Figure 28: Optional M9000-561 Thermal Barrier
Barrier
Drive
Shaft
Machine Screws
Flange
Nuts
Figure 29: Installing the Drive
Shaft into the Thermal Barrier
Figure 30: Installing the Barrier